OR 4 Internal Loads<br />

Load name Ext. Voltage Amps Percentage Watts Usage Effective Wattage Sensible btu/h Latent btu/h<br />

anesthia machine 1 120 13.5 66% 1,076 100% 1,076 3,670 0<br />

Pix 1 120 3 28% 100 100% 100 341 0<br />

Computer 7 120 12.6 26% 385 100% 385 1,314 0<br />

Blood Refrigerator 1 120 1.5 41% 73 100% 73 250 0<br />

Monitor 3 120 3.6 24% 305 100% 305 1,042 0<br />

head lamp 1 120 1.7 90% 184 100% 184 626 0<br />

head lamp 2 1 120 7.1 90% 765 100% 765 2,610 1<br />

Warmer 1 120 12 32% 456 100% 456 1,556 0<br />

Bovie 2 250 4 44% 884 10% 88 302 0<br />

fluid warmer 1 120 1 32% 38 100% 38 130 0<br />

People (active) 5 1,250 1,500<br />

Patient 1 225 105<br />

Lighting 10 720 100% 720 2,457 0 Total<br />

TOTAL 15,772 1,606 17,378<br />

2-22 Kaiser OR Loads rev2 Project No. 09104<br />

Page 21