OR 3 Internal Loads<br />

Load name Ext. Voltage Amps Percentage Watts Usage Effective Wattage Sensible btu/h Latent btu/h<br />

anesthia machine 1 120 13.5 66% 1,076 100% 1,076 3,670 0<br />

Pix 1 120 3 28% 100 100% 100 341 0<br />

Computer 3 120 5.4 26% 165 100% 165 563 0<br />

Blood Refrigerator 1 120 1.5 41% 73 100% 73 250 0<br />

Monitor 1 120 3.6 24% 102 100% 102 347 0<br />

Bovie 1 120 7.1 44% 377 10% 38 128 0<br />

fluid warmer 1 120 1 32% 38 100% 38 130 0<br />

argon beam quagulator 1 120 11 59% 780 3% 23 80 0<br />

People (active) 5 1,250 1,500<br />

Patient 1 225 105<br />

Lighting 6 720 100% 720 2,457 0 Total<br />

TOTAL 9,441 1,605 11,046<br />

2-22 Kaiser OR Loads rev2 Project No. 09104<br />