24.08.2013 Views

Download project report.

Download project report.

Download project report.

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Operating Room Lighting Replacement<br />

The operating rooms are served by two air handlers (AHU 5 & 7). Air Handler 7 handles 8 of the 12 operating rooms,<br />

and an even higher percentage of the required air; 74%, or 12,637 CFM, based on the May 31, 2009 air balance. This is<br />

57.7% of the 21,900 CFM air handler’s capacity. Air handler 5 is a 21,200 CFM air handler, which distributes a total of<br />

4,435 CFM to the remaining 4 operating rooms. The operating rooms are constant volume, 100% outdoor air units<br />

with hot water reheat. All of the air handlers in the hospital are served by a common chiller and steam boiler plant. Air<br />

is supplied overhead around the patient and onto the surgeons, and returned at floor level at the perimeter of the<br />

operating room. The schedules associated with this equipment are available in Appendix I.<br />

Figure 3: OR Supply Grille<br />

The units are controlled by a Johnson Controls Metasys system.<br />

Local control and thermostats are located in each of the surgical<br />

suites. The operating rooms are maintained in condition appropriate<br />

for surgery at all times. Room temperature is controlled by resetting<br />

the air handler’s supply air temperature to meet the maximum load<br />

on the system, and then incorporating reheat to obtain the required<br />

condition for the operating room, which typically is kept between<br />

65°F and 68°F. No humidity control is currently utilized. This<br />

control strategy has also been utilized at Petaluma Valley Hospital,<br />

although with a Delta Control system.<br />

The chiller plant consists of three water cooled chillers: 2 Centrifugal York chillers at 450 and 250 tons, and 1 150 Ton<br />

York YT screw chiller. These chillers are being utilized at a 43 degree supply temperature and a 20°F delta T. When<br />

load is increased facilities usually lowers the supply temperature. The heating hot water plant consists of 2 Bryan<br />

LMB750 steam boilers. The field readings indicate a supply of 320°F and 10 psi, and a return temperature of 120 F.<br />

Currently the associated air handlers are not meeting the requested setpoint. When plant field readings were taken the<br />

outdoor air temperature was above the limit of the air handlers, and the units were unable to hold the requested<br />

setpoint of 53°F. Air handler 5 was at 57.5°F, and air handler 7 was at 58.6°F. These units have passed their<br />

expected lifespan, and will be replaced. The new design will not be a direct replacement, but a transition to a common<br />

152,000 CFM air handler with a fan motor over 200 HP.<br />

Petaluma Valley Hospital’s surgery center consists of 4 operating suites, the layout of which is available in Appendix<br />

II. The operating rooms are denoted as Operating Rooms 1-3 & ORTHO. The facility is a two story hospital, with the<br />

surgical facilities being on the first floor. These are served by a single two speed air handling unit. Appendix III<br />

contains each OR’s specifications, the metered supply and return air data and the associated economic analysis of the<br />

OR LED replacement. Note that although the surgical suites are only utilized 68 hours a week, they must be<br />

Salas O’Brien Engineers | expect a difference | Project No. 09104<br />

Page 3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!