OR 12 Internal Loads<br />

Load name # Voltage Amps Percentage Watts Usage Effective Wattage Sensible btu/h Latent btu/h<br />

anesthia machine 1 120 13.5 66% 1,076 100% 1,076 3,670 0<br />

Pix 1 120 3 28% 100 100% 100 341 0<br />

Blood Refrigerator 1 120 1.5 41% 73 100% 73 250 0<br />

Computer 5 - - - 275 100% 275 938 0<br />

Warmer 1 120 9.5 32% 361 100% 361 1,232 0<br />

Bovie (bear hugger) 1 120 7.1 44% 377 10% 38 128 0<br />

People (active) 5 1,250 1,500<br />

Patient 1 225 105<br />

Lighting 7 520 100% 520 1,774 0 Total<br />

TOTAL 9,809 1,605 11,414<br />

2-22 Kaiser OR Loads rev2 Project No. 09104<br />