You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Air Handler Operation for Equipment Removal<br />
This section is available as background to clarify why an increase in utility energy consumption will occur with the<br />
removal of internal loads from an operating room (OR). As seen in Figure A6-1 each air handler services a number of<br />
Operating Rooms. Due to the codes dictating operating room airflow, each OR must be supplied with a minimum<br />
outdoor air supply, and thus is a Constant Volume 100% outdoor air assembly. These ORs all require a certain heat<br />
load to be removed, signified by the Q’s. Q is dictated by the internal load from equipment, lighting, occupancy, and<br />
other heat gain. In the example below OR 2 requires 7,560 BTUH to be removed. With the supplied air, an air<br />
temperature differential of 7° F between the supply and return is required to meet that load. Therefore, operating<br />
rooms 1 and 3 will require the supplied air to be reheated by the specified amount in order to meeting that room’s set<br />
point. If equipment is removed from either OR 1 or 3 their respective internal loads (Q) will be reduced, but the drop in<br />
cooling load will be picked up by the reheat coils.<br />
Figure A6-1: Air Handler Airflow Diagram<br />
OTHER AHU TYPES<br />
This is a different in single zone, multizone or VAV assemblies. For these scenarios an equipment load reduction is a<br />
direct decrease in HVAC load, and in the case of variable airflow system a decrease in fan energy. The reheat required<br />
to maintain setpoint will only occur under heating conditions<br />
Salas O’Brien Engineers | expect a difference | Project No. 09104<br />
Page 79