G2-2 Series Interbus-S Quick Start Manual<br />

M23 Interbus-S Communication Module<br />

Upon power up, the LEDs indicate the status of the unit. The Power Module of the G2-2 Interbus-S node has<br />

four LEDs; two for internal fuse integrity and two for Aux. Power status. The Communication module also<br />

has four status LEDs which are described below.<br />

LED Name<br />

TR<br />

Color Status Description<br />

(Transmit /<br />

Receive)<br />

RD<br />

Green ON Active when PCP communication is made over the Interbus-S Network<br />

(Remote Bus<br />

Disable)<br />

Red ON On when the outgoing remote bus is switched off.<br />

BA<br />

(Bus Active)<br />

Green ON Bus is active.<br />

CC<br />

(Cable Check)<br />

+24V/F1<br />

(VLV/OUT)<br />

+24V/F2<br />

(NODE/IN)<br />

Green ON The cable connection is good, and the Interbus-S Master is not in reset<br />

Green<br />

Green Red<br />

Green<br />

Green Red<br />

OFF No DC Power present at +24V VLV / OUT pin on Aux. Power connector.<br />

ON DC Power applied to +24V VLV / OUT pin on Aux. Power Connector.<br />

OFF<br />

Internal fuse F1 is OK (valid only when power is applied to<br />

+24V VLV / OUT pin on Aux. Power connector).<br />

ON<br />

Internal fuse F1 is open; No power is internally provided to valves or<br />

outputs. Communication NOT affected.<br />

OFF No DC Power present at +24V NODE / IN pin on Aux. Power connector.<br />

ON DC Power applied to+24V NODE / IN pin on Aux. Power connector.<br />

OFF<br />

Internal fuse F2 is OK (valid only when power is applied to<br />

+24V NODE / IN pin on Aux. Power connector.<br />

ON<br />

Internal fuse F2 is open; No power is internally provided to node<br />

electronics or inputs. Communication Node will not function.<br />

TDG22ISQS3-0 5/07<br />

Subject to change without notice<br />

www.numatics.com/fieldbus<br />

Page 15