0054.0...15 CO/BO: Act. control word 1 / Act CtrlWd1<br />

Access level: 3 P-Group: Commands Data type: Unsigned16<br />

Unit: - Calculated: - Data set: -<br />

© <strong>Siemens</strong> AG 2008 All Rights Reserved<br />

SINAMICS G120 <strong>Control</strong> <strong>Units</strong> CU240E/S, Edition 07/2008<br />

Parameters<br />

List of Parameters<br />

Description: Displays first control word of inverter (in bit format) and can be used to diagnose which commands are active.<br />

Bit field: Bit Signal name 1 signal 0 signal FP<br />

00 ON/OFF1 Yes No -<br />

01 OFF2: Electrical stop No Yes -<br />

02 OFF3: Fast stop No Yes -<br />

03 Pulse enable Yes No -<br />

04 RFG enable Yes No -<br />

05 RFG start Yes No -<br />

06 Setpoint enable Yes No -<br />

07 Fault acknowledge Yes No -<br />

08 JOG right Yes No -<br />

09 JOG left Yes No -<br />

10 <strong>Control</strong> from PLC Yes No -<br />

11 Reverse (setpoint inversion) Yes No -<br />

13 Motor potentiometer MOP up Yes No -<br />

14 Motor potentiometer MOP down Yes No -<br />

15 CDS Bit 0 (Hand/Auto) Yes No -<br />

Notice: r0054 is identical to r2036 if USS is selected as command source via P0700 or P0719.<br />

r0055.0...15 CO/BO: Act. control word 2 / Act CtrlWd2<br />

PM240 Access level: 3 P-Group: Commands Data type: Unsigned16<br />

Unit: - Calculated: - Data set: -<br />

Description: Displays additional control word of inverter (in bit format) and can be used to diagnose which commands are active.<br />

Bit field: Bit Signal name 1 signal 0 signal FP<br />

00 Fixed frequency Bit 0 Yes No -<br />

01 Fixed frequency Bit 1 Yes No -<br />

02 Fixed frequency Bit 2 Yes No -<br />

03 Fixed frequency Bit 3 Yes No -<br />

04 Drive Dataset (DDS) Bit 0 Yes No -<br />

05 Drive Dataset (DDS) Bit 1 Yes No -<br />

08 Enable PID Yes No -<br />

09 Enable DC brake Yes No -<br />

11 Enable Droop Yes No -<br />

12 Torque control Yes No -<br />

13 External fault 1 No Yes -<br />

15 Command Dataset (CDS) Bit 1 Yes No -<br />

Notice: r0055 is identical to r2037 if USS is selected as command source via P0700 or P0719.<br />