© <strong>Siemens</strong> AG 2008 All Rights Reserved<br />

SINAMICS G120 <strong>Control</strong> <strong>Units</strong> CU240E/S, Edition 07/2008<br />

Parameters<br />

List of Parameters<br />

Index: [0] = Analog input 0 (AI0)<br />

[1] = Analog input 1 (AI1)<br />

Dependency: Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to be generated.<br />

p0759[0...1] Value x2 of AI scaling / Value x2:AI scal.<br />

Access level: 2 P-Group: Terminals Data type: FloatingPoint32<br />

Quick comm. NO Active: NO Data set: -<br />

Can be changed: U, T Calculated: -<br />

Min Max Factory setting<br />

-20 20 10<br />

Description: Sets value of x2 as described in P0757 (AI scaling).<br />

Index: [0] = Analog input 0 (AI0)<br />

[1] = Analog input 1 (AI1)<br />

Notice: The value x2 of AI scaling P0759 must be greater than the value x1 of AI scaling P0757.<br />

p0760[0...1] Value y2 of AI scaling / Value y2:AI scal.<br />

Access level: 2 P-Group: Terminals Data type: FloatingPoint32<br />

Quick comm. NO Active: NO Data set: -<br />

Can be changed: U, T Calculated: -<br />

Min Max Factory setting<br />

-99999.9 [%] 99999.9 [%] 100.0 [%]<br />

Description: Sets value of y2 in [%] as described in P0757 (AI scaling).<br />

Index: [0] = Analog input 0 (AI0)<br />

[1] = Analog input 1 (AI1)<br />

Dependency: Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to be generated.<br />