p0291[0...2] Inverter protection / Inverter protect.<br />

Access level: 4 P-Group: Converter Data type: Unsigned16<br />

Quick comm. NO Active: YES Data set: DDS<br />

Can be changed: T Calculated: -<br />

© <strong>Siemens</strong> AG 2008 All Rights Reserved<br />

SINAMICS G120 <strong>Control</strong> <strong>Units</strong> CU240E/S, Edition 07/2008<br />

Parameters<br />

List of Parameters<br />

Min Max Factory setting<br />

- - 0001 bin<br />

Description: Bit 00 for enabling/disabling automatic pulse frequency reduction at output frequencies below 2 Hz.<br />

The benefit is to reduce the noises at frequencies below 2 Hz.<br />

Bit 02 shows if phase loss detection (input phase) of 3 phase inverters is enabled after factory reset.<br />

Default setting of phase loss is disabled for FSA - FSC. FSD and greater it is enabled.<br />

Bit field: Bit Signal name 1 signal 0 signal FP<br />

01 reserved Yes No -<br />

02 Phase loss detection enable Yes No -<br />

Note: See P0290 (inverter overload reaction)<br />

p0292 Inverter temperature warning / Inv. temp. warn.<br />

Access level: 3 P-Group: Converter Data type: Unsigned16<br />

Quick comm. NO Active: NO Data set: -<br />

Can be changed: U, T Calculated: -<br />

Min Max Factory setting<br />

0 [°C] 25 [°C] 5 [°C]<br />

Description: Defines the temperature difference (in °C) between the overtemperature trip threshold (F0004) and the warning<br />

threshold (A0504) of the inverter.<br />

The trip threshold is stored internally by the inverter and cannot be changed by the user.<br />

p0294 Inverter I2t warning / Inv. I2t warn.<br />

Access level: 4 P-Group: Converter Data type: FloatingPoint32<br />

Quick comm. NO Active: NO Data set: -<br />

Can be changed: U, T Calculated: -<br />

Min Max Factory setting<br />

10.0 [%] 100.0 [%] 95.0 [%]<br />

Description: Defines the [%] value at which warning A0505 (inverter I2t) is generated.<br />

Inverter I2t calculation is used to determine a maximum tolerable period for inverter overload.<br />

The I2t calculation value is deemed = 100 % when this maximum tolerable period is reached.<br />

Dependency: • The output current of the inverter has been reduced.<br />

• The value of I2t does not exceed 100 %.<br />

Note: P0294 = 100 % corresponds to stationary nominal load.<br />

p0295 Inverter fan off delay time / Fan delay time<br />

Access level: 3 P-Group: Terminals Data type: Unsigned16<br />

Quick comm. NO Active: NO Data set: -<br />

Can be changed: U, T Calculated: -<br />

Min Max Factory setting<br />

0 [s] 3600 [s] 0 [s]<br />

Description: Defines inverter fan switch off delay time in seconds after drive has stopped.<br />

Note: Setting to 0, inverter fan will switch off when the drive stops, that means no delay.<br />