Infocal 5 Communication Description Version 2.00<br />
4.2.3. Request from master<br />
Name Length in bytes Value Description<br />
Start 1 10H<br />
C Field 1 5BH/7BH Request for UD2<br />
A Field 1 --H<br />
Check Sum 1 --H<br />
Stop 1 16H<br />
4.2.4. Response from slave<br />
Name Length in bytes Value Description<br />
Start 1 68H<br />
L Field 1 --H<br />
L Field 1 --H<br />
Start 1 68H<br />
C Field 1 08H<br />
A Field 1 --H<br />
CI Field 1 72H<br />
Ident. Nr. 4 --H 8 BCD packed Identification number<br />
Manufr. 2 5068H Manufacture ID = “TCH”<br />
Version 1 01H INFOCAL5 protocol version.<br />
Medium 1 04H / 0CH Heat outlet / Heat inlet<br />
Access No. 1 --H Increments for each RSP_UD<br />
Status 1 00H Application errors<br />
Signature 2 0000H For future use<br />
DIF 1 0FH Sp1 Manufacture specific data<br />
Param<br />
1 10H Status structure<br />
select<br />
StatusInfo 1 --H Bit 7: Write OK = 1,Not OK = 0<br />
Bit 6: HWLock On = 1,Not On = 0<br />
Bit 5: High Res On = 1,Not On = 0<br />
Bit 4 – 0: Not used<br />
ErrorCode 1 --H ErrorCode on display.<br />
See Appendix B.<br />
SW version 4 --H<br />
ResetDeltaTStatus 1 --H Percent of reset status.<br />
Check Sum 1 --H<br />
Stop 1 16H<br />
10