Infocal 5 Communication Description Version 2.00<br />

5.4.3. Request from master<br />

Name Length in bytes Value Description<br />

Start 1 10H<br />

C Field 1 5BH/7BH Request for UD2<br />

A Field 1 --H<br />

Check Sum 1 --H<br />

Stop 1 16H<br />

5.4.4. Response from slave<br />

Name Length in bytes Value Description<br />

Start 1 68H<br />

L Field 1 --H<br />

L Field 1 --H<br />

Start 1 68H<br />

C Field 1 08H<br />

A Field 1 --H<br />

CI Field 1 72H<br />

Ident. Nr. 4 00.00.00.01.H 8 BCD packed Identification number<br />

Manufr. 2 5068H Manufacture ID = “TCH”<br />

Version 1 01H INFOCAL5 protocol version.<br />

Medium 1 04H Heat outlet<br />

Access No. 1 01H Increments for each RSP_UD<br />

Status 1 00H Application errors<br />

Signature 2 0000 For future use<br />

H<br />

DIF 1 0FH Sp1 Manufacture specific data<br />

Param select 1 10H Status structure<br />

StatusInfo 1 --H Write OK/Not OK, HW Lock, High<br />

Resolution, Module no.<br />

ErrorCode 1 --H ErrorCode on display.<br />

See Appendix B.<br />

SW version 4 --H<br />

ResetDeltaTStatus 1 --H Percent of reset status.<br />

Check Sum 1 --H<br />

Stop 1 16H<br />

23