Infocal 5 Communication Description Version 2.00<br />

10. Appendix B<br />

10.1. Data type F<br />

Type F = Compound CP32: Date and Time<br />

2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0<br />

2 15 2 14 2 13 2 12 2 11 2 10 2 9 2 8<br />

2 23 2 22 2 21 2 20 2 19 2 18 2 17 2 16<br />

2 31 2 30 2 29 2 28 2 27 2 26 2 25 2 24<br />

min: UI6 [bit 0 to 5] <br />

hour: UI5 [bit 8 to 12 <br />

day: UI5 [bit 16 to 20] <br />

month: UI4 [bit 24 to 27] <br />

year: UI7 [bit 21 to 23, 28 to 31] <br />

hundred year: UI7 [bit 13 to 14] <br />

The year is 1900 + 100*hundred year + year<br />

10.2. ErrorCode on display.<br />

The ErrorCode byte is coded as:<br />

1. Error on Forward temperature for more than 1 hour Bit 0<br />

2. Error on Reverse temperature for more than 1 hour Bit 1<br />

3. Internal EEPROM error Bit 2<br />

4. Difference temperature but no flow for more than 48 hours Bit 3<br />

5. Overflow error. Flow 1 input > Qsmax Bit 4<br />