Infocal 5 Communication Description Version 2.00<br />

5.2. Set-up of Identification number<br />

5.2.1. Request from master<br />

Name Length in bytes Value Description<br />

Start 1 68H<br />

L Field 1 --H<br />

L Field 1 --H<br />

Start 1 68H<br />

C Field 1 53H/73H SND_UD<br />

A Field 1 --H<br />

CI Field 1 51H Data send (master to slave)<br />

DIF 1 0CH 8 digit BCD<br />

VIF 1 79H Identification<br />

Value 4 -- Identification number<br />

Check Sum 1 --H<br />

Stop 1 16H<br />

5.2.2. Response from slave<br />

Name Length in bytes Value Description<br />

Ack 1 E5H Acknowledge to master<br />

5.3. Set-up of Date & Time<br />

5.3.1. Request from master<br />

Name Length in bytes Value Description<br />

Start 1 68H<br />

L Field 1 --H<br />

L Field 1 --H<br />

Start 1 68H<br />

C Field 1 53H/73H SND_UD<br />

A Field 1 --H<br />

CI Field 1 51H Data send (master to slave)<br />

DIF 1 04H 32 bit integer<br />

VIF 1 6DH Date & Time<br />

Value 4 --H Date & Time according to data Type F<br />

Check Sum 1 --H<br />

Stop 1 16H<br />

5.3.2. Response from slave<br />

Name Length in bytes Value Description<br />

Ack 1 E5H Acknowledge to master<br />

21