Infocal 5 Communication Description Version 2.00<br />
5. Set-up parameters<br />
5.1. Set-up of Bus Address<br />
5.1.1. Request from master<br />
Name Length in bytes Value Description<br />
Start 1 68H<br />
L Field 1 --H<br />
L Field 1 --H<br />
Start 1 68H<br />
C Field 1 53H/73H SND_UD<br />
A Field 1 --H<br />
CI Field 1 51H Data send (master to slave)<br />
DIF 1 01H 8 Bit integer<br />
VIF 1 7AH Bus Address<br />
Value 1 --H Bus Address<br />
Check Sum 1 --H<br />
Stop 1 16H<br />
5.1.2. Response from slave<br />
Name Length in bytes Value Description<br />
Ack 1 E5H Acknowledge to master<br />