Infocal 5 Communication Description Version 2.00<br />

DIF 1 0BH BCD 6<br />

VIF 1 5AH Flow Temperature 100<br />

m°C<br />

Value 3 -- FWTemperature<br />

DIF 1 0BH BCD 6<br />

VIF 1 5EH Return Temperature 100<br />

m°C<br />

Value 3 -- RVTemperature<br />

DIF 1 0BH BCD 6<br />

VIF 1 61H Temperature difference<br />

10 mK<br />

Value 3 -- DeltaT<br />

DIF 1 04H 32 bit integer<br />

VIF 1 22H On Time hours<br />

Value 4 -- HourCounter<br />

DIF 1 04H 32 bit integer<br />

VIF 1 6DH Date & Time<br />

Value 4 -- Date & Time according<br />

to data Type F<br />

DIF 1 01H 8 bit integer<br />

VIF 1 FDH Select VIFE table FDH<br />

VIFE 1 17H Error flags (binary)<br />

Value 1 --H ErrorCode on display.<br />

See Appendix B.<br />

Check Sum 1 --H<br />

Stop 1 16H<br />

4.2. Reading of Calculator Status<br />

4.2.1. Request from master<br />

Name Length in bytes Value Description<br />

Start 1 68H<br />

L Field 1 --H<br />

L Field 1 --H<br />

Start 1 68H<br />

C Field 1 53H/ SND_UD<br />

73H<br />

A Field 1 --H<br />

CI Field 1 51H Data send (master to<br />

slave)<br />

DIF 1 08H Selection telegram<br />

VIF 1 7FH Manufacture specific<br />

Param select 1 10H Status structure<br />

Check Sum 1 --H<br />

Stop 1 16H<br />

4.2.2. Response from slave<br />

Name Length in bytes Value Description<br />

Ack 1 E5H Acknowledge to master<br />

9