R-INSTRUKTION 087R2121 - Siemens
R-INSTRUKTION 087R2121 - Siemens
R-INSTRUKTION 087R2121 - Siemens
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Infocal 5 Communication Description Version 2.00<br />
4.7.4. Response from slave<br />
Name Length in bytes Value Description<br />
Start 1 68H<br />
L Field 1 --H<br />
L Field 1 --H<br />
Start 1 68H<br />
C Field 1 08H<br />
A Field 1 --H<br />
CI Field 1 72H<br />
Ident. Nr. 4 00.00.00.01.H 8 BCD packed Identification number<br />
Manufr. 2 5068H Manufacture ID = “TCH”<br />
Version 1 01H INFOCAL5 protocol version.<br />
Medium 1 04H Heat outlet<br />
Access No. 1 01H Increments for each RSP_UD<br />
Status 1 00H Application errors<br />
Signature 2 0000H For future use<br />
DIF 1 01H 8 bit integer<br />
VIF 1 FDH Select VIFE table FDH<br />
VIFE 1 17H Error flags (binary)<br />
Value 1 --H ErrorCode 1 – 10.<br />
See Appendix B.<br />
DIF 1 04H 32 bit integer<br />
VIF 1 6DH Date & Time according to data Type F<br />
Value 4 --H OccurredTime 1-10<br />
DIF 1 04H 32 bit integer<br />
VIF 1 6DH Date & Time according to data Type F<br />
Value 4 --H DisappearedTime 1-10<br />
DIF 1 0FH Sp1 Manufacture specific data<br />
Param select 1 21H<br />
:<br />
2AH<br />
Check Sum 1 --H<br />
Stop 1 16H<br />
1. (newest) Error in ErrorLog<br />
10. (oldest) Error in ErrorLog<br />
19