Infocal 5 Communication Description Version 2.00<br />
2.2.2. Deselecting a slave by writing to none or to select another slave<br />
2.2.2.1. Request from master<br />
Name Length in bytes Value Description<br />
Start 1 68H<br />
L Field 1 0BH<br />
L Field 1 0BH<br />
Start 1 68H<br />
C Field 1 53H SND_UD<br />
A Field 1 FDH Secondary addressing<br />
CI Field 1 52H Mode 1<br />
Ident. Nr. 4 00.00.00.<br />
00.H<br />
8 BCD packed<br />
Identification number<br />
Manufr. 2 0000H Manufacture ID<br />
Version 1 00H Calculator generation or<br />
version.<br />
Medium 1 04H / Heat outlet / Heat inlet<br />
0CH<br />
Check Sum 1 --H<br />
Stop 1 16H<br />
None or another Ident. Nr., Manufr. and Version.<br />
2.2.2.2. Response from slave<br />
NO response.<br />
2.2.3. Deselecting a slave by CI Field = 56H<br />
2.2.3.1. Request from master<br />
Name Length in bytes Value Description<br />
Start 1 68H<br />
L Field 1 0BH<br />
L Field 1 0BH<br />
Start 1 68H<br />
C Field 1 53H SND_UD<br />
A Field 1 FDH Secondary addressing<br />
CI Field 1 56H Mode 2 = deselect<br />
Ident. Nr. 4 --H 8 BCD packed<br />
Identification number<br />
Manufr. 2 5068H Manufacture ID = “TCH”<br />
Version 1 01H INFOCAL5 protocol<br />
version.<br />
Medium 1 04H / Heat outlet / Heat inlet<br />
0CH<br />
Check Sum 1 --H<br />
Stop 1 16H<br />
2.2.3.2. Response from slave<br />
Name Length in bytes Value Description<br />
Ack 1 E5H Acknowledge to master<br />