Issued: September 30, 2008<br />

8. TASK 5 – DESIGN FIRE SCENARIO - FREEBURN<br />

TESTING OF LIVING ROOM SPACE<br />

8.1 GENERAL<br />

<strong>UL</strong> designed and constructed a simulated fire setting to represent living areas that included a<br />

nominal 14x14x 8ft. height living area with open doorways at each end <strong>of</strong> the room to provide<br />

natural ventilation. A nominal 6ft. wide x 14ft. long hallway was constructed adjacent to the<br />

living area and connected with one <strong>of</strong> the two living area doorways. The living area setting was<br />

furnished with upholstered furniture, wood tables, plastic toys, lighting, wall painting and other<br />

typical furnishings. The fire scenario was allowed to progress past flashover conditions.<br />

Tests were conducted to characterize the structural fire heat release and fire growth.<br />

Instrumentation monitored temperatures and heat release rate and identified when fire control<br />

had occurred. Temperatures and smoke were monitored at the doorway and hallway opening to<br />

examine the ambient conditions that would be experienced by the firefighter.<br />

8.2 TEST FACILITY<br />

The fire tests were conducted at Underwriters Laboratories large-scale fire test facility located in<br />

Northbrook, Illinois.<br />

8.2.1 Large-Scale Fire Test Building<br />

The large-scale fire test building used <strong>for</strong> this investigation houses four fire test areas that are<br />

used to develop data on the fire growth and fire suppression characteristics <strong>of</strong> <strong>com</strong>modities, as<br />

well as the fire suppression characteristics <strong>of</strong> automatic water sprinkler systems. A schematic <strong>of</strong><br />

the test facility is shown in Figure 16.<br />

Page 24 <strong>of</strong> 55