Issued: September 30, 2008<br />

End Table<br />

3.5 ft. (typ)<br />

love Seat<br />

End Table<br />

Tc Tree (7 tcs)<br />

Smokeye Tree (3 photocells)<br />

3.5 ft. (typ)<br />

3.5 ft. (typ)<br />

Tc Tc Tc<br />

Tc<br />

3.0 ft. (typ)<br />

S<strong>of</strong>a<br />

Cocktail Table<br />

Floor mounted Radiometer<br />

Tc Tc Tc<br />

Entertainment Center<br />

Tc<br />

Tc<br />

Smokeye Tree (3<br />

photocells)<br />

Tc Tc Tc<br />

Gas Analyzer<br />

Tc Tree (7 tcs)<br />

Gas Analyzer<br />

Tc<br />

8.3.1 Gas Temperature<br />

Tc Tree<br />

(7 tcs)<br />

Figure 17 – Instrumentation Map <strong>of</strong> Room and Corridor – Plan View<br />

All gas temperatures were taken with 0.0625-in. diameter inconel sheathed Type K<br />

thermocouples as shown in Figure B-1 <strong>of</strong> Appendix B. Note that this photograph shows a short<br />

immersion length thermocouple. The immersion lengths used in the actual test were<br />

significantly larger.<br />

8.3.1.1 Gas Temperature at Ceiling in Living Room<br />

The gas temperature in the primary living room space was measured with equally spaced<br />

thermocouples positioned nominally 3.5 ft. on center, 3 inches below the ceiling. Nine<br />

thermocouples were used <strong>for</strong> this test arrangement. See Figure 17 <strong>for</strong> layout.<br />

8.3.1.2 Gas Temperature at Ceiling in Corridor<br />

The gas temperature in the corridor, adjacent to the primary living room space was measured<br />

with equally spaced thermocouples positioned nominally 3.5 ft. on center, 3 inches below the<br />

ceiling, centered on the corridor width. Four thermocouples were used <strong>for</strong> this test arrangement.<br />

See Figure 17 <strong>for</strong> layout.<br />

Page 26 <strong>of</strong> 55