History Status<br />
Operation<br />
The History Status screen displays 64 frames, of 4 milliseconds each, from the Present Status screen.<br />
Note that the values for output volts and amps are updated once each millisecond. Alarms are listed<br />
in the sequence they occurred, within 1 millisecond resolution. The frames are stored in a buffer (a<br />
computer information storage technique). The buffer stores the frames in a first in, first out sequence.<br />
As a new frame enters the buffer the oldest one is released.<br />
When a designated fault occurs (see list below), the buffer stores information for the next 24 frames<br />
and then freezes (stops gathering information). At that time, the History Status screen contains<br />
40 frames before the fault, the frame when the fault occurred and 23 frames after the fault. This<br />
64-page report is a very useful diagnostic tool for the operator or Liebert Global Services. Use the Up<br />
and Down pads to view the screens.<br />
Figure 25 History status report screens<br />
HISTORY STATUS MODULE-0 04/10/97 16:49:21 FRAME 36<br />
ORDER - 000000 SITE ID - 00000 SITE TAG - 0000000<br />
**** ACTIVE ALARMS **** Output Ov-volts<br />
OUTPUT VOLTS<br />
OUTPUT AMPS<br />
OUTPUT FREQUENCY<br />
LOAD KVA<br />
BYPASS VOLTS<br />
A<br />
480<br />
420<br />
480<br />
B<br />
480<br />
420<br />
480<br />
C<br />
480<br />
420<br />
480<br />
DC<br />
LOAD<br />
349<br />
HERTZ<br />
60.0<br />
TIME<br />
UP : NEXT FRAME<br />
DOWN : PREVIOUS FRAME<br />
SELECT : EXIT<br />
HISTORY STATUS MODULE-0 04/10/97 01/17/98 16:49:21 11:21:59 FRAME36100<br />
ORDER - 000000 SITE ID - 00000 SITE TAG - 0000000<br />
**** ACTIVE ALARMS **** Batt Output Discharging Ov-volts Low Batt Warning<br />
OUTPUT VOLTS<br />
OUTPUT AMPS<br />
OUTPUT FREQUENCY<br />
LOAD OUTPUT KVAVOLTS<br />
BYPASS OUTPUTVOLTS<br />
AMPS<br />
BATTERY VOLTS<br />
OUTPUT VOLTS<br />
OUPUT AMPS<br />
BATTERY AMPS<br />
INPUT VOLTS<br />
INPUT AMPS<br />
OUPUT VOLTS<br />
OUTPUT AMPS<br />
LOAD KVA<br />
A<br />
380 480<br />
530 325<br />
480<br />
380 325<br />
480<br />
325<br />
0<br />
0<br />
480<br />
325<br />
B<br />
480 380<br />
325 530<br />
480<br />
325 380<br />
480<br />
325<br />
0<br />
0<br />
480<br />
325<br />
C<br />
480 380<br />
325 530<br />
480<br />
325 380<br />
480<br />
325<br />
0<br />
0<br />
480<br />
325<br />
DC<br />
390<br />
-645<br />
LOAD<br />
HERTZ<br />
60.0 50.0<br />
TIME<br />
349<br />
0:01<br />
UP :<br />
NEXT FRAME<br />
DOWN :<br />
PREVIOUS FRAME<br />
270<br />
SELECT :<br />
EXIT<br />
40