SECTION 29: PHYSICAL FACILITIES, DETAILS <strong>AND</strong> F<strong>IN</strong>ISHES<br />

Agency #007.05<br />

All details for alteration or expansion projects as well as for new construction shall<br />

comply with the following.<br />

A. Details.<br />

1. Compartmentation, exits, automatic extinguishing systems, and other<br />

details relating to fire prevention and fire protection shall comply with<br />

requirements listed in the NFPA referenced codes, shall be maintained at<br />

the facility and shown on the Fire Protection Plan.<br />

2. Corridor partitions, smoke stop partitions, horizontal exit partitions, exit<br />

enclosures, and fire rated walls required to have protected openings shall<br />

be effectively and permanently identified with signs or stenciling in a<br />

manner acceptable to the Health Facility Services. Such identification<br />

shall be above any decorative ceiling and in concealed spaces.<br />

3. Rooms containing bathtubs, sitz baths, showers, and water closets,<br />

subject to occupancy by patients, shall be equipped with doors and<br />

hardware which shall permit access from the outside the room.<br />

4. Glass doors, lights, sidelights, borrowed lights, and windows located within<br />

12 inches of a door jamb (with a bottom frame height of less than 60<br />

inches above the finished floor) shall be constructed of safety glass, wired<br />

glass, or plastic, break resistant material that creates no dangerous cutting<br />

edges when broken. Safety glass-tempered or plastic glazing materials<br />

shall be used for shower doors and bath enclosures. In renovation<br />

projects, only glazing within 18 inches of the floor shall be changed to<br />

safety glass, wire glass, or plastic, break-resistant material.<br />

5. Thresholds and expansion joint covers shall be installed flush with the<br />

floor surface to facilitate use of wheelchairs and carts. Expansion and<br />

seismic joints shall be constructed to restrict the passage of smoke.<br />

6. Grab bars shall be provided in all patients' toilets, showers, tubs, and sitz<br />

baths. The bars shall have one and one-half inch clearance to walls and<br />

shall have sufficient strength and anchorage to sustain a concentrated<br />

load of 250 pounds.<br />

7. Lavatories and hand washing stations shall be securely anchored to<br />

withstand an applied downward vertical load of not less than 250 pounds<br />

on the front of the fixture.<br />