<strong>solaris</strong> <strong>24PC</strong>, <strong>30PC</strong><br />

15. Onboard Adjustments<br />

Potentiometer<br />

adjustment cover<br />

15.1 The boiler incorporates 4 potentiometers<br />

and a bank of dip switches to allow adjustment<br />

to its pre-set parameters. These are situated on<br />

the rear of the control panel. (figure 19)<br />

POTENTIOMETERS<br />

DIP SWITCHES<br />

23<br />

P7<br />

P5<br />

P2<br />

P4<br />

Figure 19<br />

The potentiometers can easily be accessed by<br />

removing the cover on the rear of control<br />

panel (Figure 20). However, to reach the dip<br />

switches, the control panel must be opened.<br />

P7 – Ignition fan ramp<br />

(default setting 4 0’clock)<br />

P5 – Anti cycle timer adjustment<br />

(default setting 6 0’clock)<br />

P2 - Boiler range adjuster<br />

(default setting 4 0’clock)<br />

P4 – Maximum Fan sped adjustment<br />

(default setting 4 0’clock)<br />

15.2 Setting the maximum c/heating flow<br />

temperature: The boiler is dispatched with a<br />

maximum flow temperature factory set to 85°C.<br />

Where a lower maximum temperature is required<br />

such as in the case of under-floor heating,<br />

the factory setting can be altered between a<br />

maximum of 50°C and a minimum of 30ºC,<br />

by setting dip switch '6' into ON position.<br />

15.3 Setting the 45 second delay: The boiler is<br />

factory set to exclude the delay of 45 seconds<br />

before re-ignition between the closing of a hot<br />

water faucet and CH start-up. This delay can be<br />

set to 45 seconds by setting dip switch ‘3’<br />

(figure 19) into the OFF position.<br />

15.4 255 seconds delay setting: The boiler is<br />

capable of up to 255 seconds ignition delay (anti<br />

cycling time) before re-ignition following burner<br />

shut down on the primary hydraulic water<br />

reaching its set temperature. This delay can be<br />

increased up to a maximum of 255 seconds by<br />

turning potentiometer P5 (Figure 19) clockwise.<br />

15.5 Pump working mode setting: The boiler has<br />

a factory set to operate the pump for pre-purge and<br />

post-purge times (45 sec.). This delay can be<br />

excluded by fitting dipswitch ‘2’ (figure 19) into<br />

ON position. However, this may then cause the<br />

boiler over-heat thermostat to trip out.<br />

15.6 The maximum and minimum heat output for<br />

heating is adjusted via potentiometer P2 (figure<br />

19) which changes the fan speed and thus the gas<br />

rate. It is not necessary to make further<br />

adjustments.<br />

Page 23