SIMATIC PCS 7 process control system
SIMATIC PCS 7 process control system
SIMATIC PCS 7 process control system
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Industrial Ethernet switches<br />
■ ESM (electrical) and OSM (optical) with 2 ring ports each<br />
for transmission rates up to 100 Mbit/s and, depending on<br />
the type, up to 8 ports (RJ45, ITP or BFOC) for data terminals<br />
or network segments<br />
■ SCALANCE X414-3E with<br />
- 2-Gigabit Ethernet ports for Gigabit rings: electrical or<br />
optical 1)<br />
- Up to 20 electrical 100-Mbit/s ports (12 integrated and 8<br />
per extender) for connecting data terminals or network<br />
segments<br />
- 2 optical ports 1) for 100-Mbit/s rings<br />
- Up to 10 optical 100-Mbit/s ports 1) , of which 8 per<br />
extender for connecting data terminals or network segments<br />
■ SCALANCE X208 with 8 ports for transmission rates up to<br />
100 Mbit/s, suitable for electrical Industrial Ethernet structures<br />
with linear, star or ring topology<br />
■ SCALANCE X204-2 with 2 optical ports and 4 electrical<br />
ports for transmission rates up to 100 Mbit/s, suitable for<br />
optical Industrial Ethernet structures with linear or ring<br />
format<br />
1) In conjunction with media module<br />
As a result of their interference resistance and high availability,<br />
optical rings are preferably used for the plant bus and<br />
OS LAN (terminal bus). Both the OSM/ESM switches and the<br />
SCALANCE X414-3E can be used as the redundancy manager<br />
in a ring. The redundancy manager recognizes the failure of a<br />
transmission link or a switch in the ring and activates the<br />
standby link within 0.3 seconds.<br />
The standby function of the OSM/ESM switches enable the<br />
plant bus to be designed as a redundant double ring if necessary.<br />
This configuration also tolerates double faults such as an<br />
OSM/ESM failure on ring 1 and simultaneous opening-up of<br />
the bus cable of ring 2. The switch operated at standby on ring<br />
2 recognizes failure of the redundant partner via a connection<br />
cable, and activates the standby bus.<br />
Technical specifications for Industrial Ethernet<br />
Plant bus / OS LAN<br />
Number of stations<br />
Length of the network<br />
• Local network<br />
• WAN<br />
Topology<br />
Industrial Ethernet<br />
1,023 per network segment<br />
(IEEE 802.3)<br />
Electrical: up to approx. 5 km<br />
Optical: up to approx. 150 km<br />
Worldwide with TCP/IP<br />
Linear, tree, ring, star<br />
Industrial Wireless LAN (IWLAN)<br />
<strong>SIMATIC</strong> <strong>PCS</strong> 7 offers the possibility for integrating remote<br />
clients into the OS LAN via Industrial Wireless LAN:<br />
■ OS clients based on <strong>SIMATIC</strong> <strong>PCS</strong> 7 basic devices<br />
ES/OS/BATCH/IT communicate via two SCALANCE W788-<br />
1PRO units. One is operated as an access point on the<br />
OS LAN, the other as an Industrial Ethernet client module<br />
on the remote client on site.<br />
■ Remote clients based on a mobile computer use a CP 7515<br />
communications <strong>process</strong>or in the CardBus slot for communication<br />
with the access point.<br />
From the remote client, the user can access an engineering<br />
station per remote desktop or PC Anywhere.<br />
All components used are very rugged, apply state-of-the-art<br />
authentication and encryption procedures, and guarantee<br />
high reliability of the radio channel.<br />
highlights<br />
Industrial Ethernet<br />
■ Universally implementable:<br />
– In all sectors<br />
– In office environments just as in harsh industrial environments<br />
■ Fast commissioning through:<br />
– Simple connection <strong>system</strong><br />
– Local assembly using the FastConnect cabling <strong>system</strong><br />
together with RJ45 technology<br />
■ MV interference resistance through optical transmission<br />
media<br />
■ Continuous monitoring of network components through<br />
a simple yet effective signaling concept<br />
■ Plant-wide clock <strong>system</strong> for exact assignment of events<br />
within the complete plant<br />
■ High availability thanks to redundant network topologies<br />
■ Resistant to power failure through fast switchover to<br />
redundant <strong>system</strong><br />
■ High flexibility through reaction-free expansion of existing<br />
plants<br />
■ Scalable performance with switching technology for<br />
almost unlimited communications performance<br />
■ Modern and future-oriented network components,<br />
e.g. SCALANCE X Industrial Ethernet switches<br />
■ Investment security through compatible further developments<br />
Communication 43