Heatrae Sadia Electromax Installation Guide - Advanced Water

Heatrae Sadia Electromax Installation Guide - Advanced Water

Heatrae Sadia Electromax Installation Guide - Advanced Water

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

3.3 Pipework, Fittings and Outlet / Terminal<br />

Fittings<br />

<br />

<br />

systems and have a rated operating<br />

pressure of at least 6 bar. Where plastic<br />

<br />

pressure must be achievable at outlet<br />

temperatures that can be expected within<br />

the hot water distribution pipework. If in<br />

doubt, consult the manufacturer of the<br />

<br />

The <strong>Electromax</strong> unvented cylinder can<br />

be used in conjunction with most types of<br />

<br />

mixer showers or taps to have balanced<br />

pressure hot and cold water supplies, in<br />

these instances the balanced cold water<br />

supply should be teed off the supply to the<br />

<strong>Electromax</strong> immediately after the Cold <strong>Water</strong><br />

Combination Valve (see diagram 5).<br />

Branches to cold outlets where drinking<br />

water may be drawn should be taken<br />

directly from the main supply before the<br />

Cold <strong>Water</strong> Combination Valve to avoid<br />

the possibility of warm expanded water<br />

being drawn from cold taps.<br />

3.4 Treatment of the Primary (Central<br />

Heating) Circulating System<br />

Primary water circulating systems will be<br />

subject to corrosion unless an appropriate<br />

water treatment is applied. Without treatment<br />

<br />

over time as corrosion sludge accumulates<br />

within the system, risking damage to the pump<br />

and valves, system noise and circulation<br />

problems.<br />

Unvented Cylinder<br />

Temperature /<br />

Pressure Relief<br />

Valve<br />

Tundish<br />

Expansion<br />

Vessel<br />

<strong>Electromax</strong> Housing<br />

Unvented System<br />

Primary System<br />

Cold Balanced<br />

Draw Off (to<br />

Mixer Outlets)Cold Draw Off<br />

(to Drinking<br />

<strong>Water</strong> Outlets)<br />

Isolating<br />

Valve<br />

Discharge Pipe<br />

Cylinder Drain<br />

Diagram 5 System Schematic - DHW Cylinder<br />

Expansion Valve<br />

Discharge<br />

Cold <strong>Water</strong><br />

Combination<br />

Valve<br />

Cold <strong>Water</strong><br />

Mains Supply<br />

10 <strong>Installation</strong> & Servicing Instructions