diagnose problems with the <strong>Electromax</strong><br />

unit. These checks should be carried out<br />

by a competent installer or an authorized<br />

<strong>Heatrae</strong> <strong>Sadia</strong> service engineer or agent. A<br />

range of replacement parts (see Section 9.2)<br />

is available should any major component<br />

be suspected as faulty. The instructions in<br />

Section 9.2 detail how to remove and replace<br />

key components and assemblies. Observe<br />

all safety warnings before removing any<br />

components, if in doubt contact <strong>Heatrae</strong><br />

<strong>Sadia</strong> for further advice.<br />

Diagram 23 Electric Boiler Fault Finding<br />

Supply Faults<br />

BOILER ELEC TR ICAL<br />

SUPPLY FAULT<br />

FINDING<br />

IS 240V<br />

SUPPLY AT 24<br />

HOUR & 45AMP<br />

TERM INALS<br />

YES<br />

DOES THE<br />

CH ON SW ITCH<br />

ILLUM INATE W HEN<br />

ON<br />

YES<br />

NO<br />

NO<br />

NO<br />

CHECK ELECTRICAL<br />

SUPPLIES<br />

CHECK SW ITCH<br />

CHECK FOR SHORT<br />

CIRCUITS.IF OK<br />

REPLACEFUSEFS1<br />

Diagram 22 Electric Boiler Fault Finding<br />

Master<br />

ELECTRIC BOILER<br />

NOT W ORKING<br />

IS CH<br />

SW ITC H O N<br />

& ILLU M INATED<br />

NO<br />

GO TO SUPPLY<br />

FAU LT FINDING<br />

SECTION<br />

YES<br />

IS THERE<br />

8V DC O N<br />

C1ON CONTROL<br />

PCB<br />

YES<br />

NO<br />

REPLACE THE<br />

CONTROLPCB<br />

YES<br />

REPLACE THE<br />

STATUS DISPLAY PCB<br />

IS THE<br />

ALARM STATUS<br />

INDICATOR<br />

ILLU M INATED<br />

YES<br />

GO TO ALARM<br />

FAU LT FINDING<br />

SECTION<br />

Diagram 24 Electric Boiler Fault Finding<br />

Alarm 1<br />

NO<br />

ALARM TRIPS ON<br />

POW ER UP.BOTH<br />

DEMAND AND ALARM<br />

INDICATORS ARE RED<br />

IS THE<br />

BOILER H O T<br />

NO<br />

IS THE<br />

DEMAND STATUS<br />

INDICATOR<br />

FLASHING<br />

YES<br />

NO<br />

GO TO DEMAND<br />

INDICATOR FAULT<br />

FINDING SECTION<br />

YES<br />

IS THE<br />

PUM P<br />

RUNNING<br />

YES<br />

RUN SYSTEM IN<br />

ALARM M ODE TO<br />

ALLOW PUM P TO<br />

COOLSYSTEM<br />

BEFORE RESETTING<br />

DOES<br />

THE DEM AND<br />

INDIC ATO R STO P<br />

FLASHING AFTER<br />

3MINS<br />

NO<br />

GO TO DEMAND<br />

INDICATOR FAULT<br />

FINDING SECTION<br />

NO<br />

HAS<br />

THE 3 AM P<br />

PANEL MOUNTED<br />

FUSE BLOW N<br />

YES<br />

REPLACE FUSE<br />

YES<br />

NO<br />

NO<br />

CHECK FOR PRIMARY<br />

WATERFLOW<br />

NO<br />

CHECK SERVICE<br />

VALVES ARE OPEN.<br />

CHECK AND REPLACE<br />

PUM P<br />

YES<br />

YES<br />

REPLACE THE<br />

CONTROLPCB<br />

YES<br />

NO<br />

CHANGE MAIN<br />

PCB<br />

IS<br />

CONN 3<br />

OPEN CIRCUIT<br />

NO<br />

THERE IS NOWATER<br />

IN THE SYSTEM .<br />

SW ITC H O FF<br />

IMMEDIATELY.<br />

CHECK AND REFILL<br />

BEFORE RESTARTING<br />

NOTE:<br />

DO NOT CHECK ELEM ENT<br />

RESISTANCE W ITH PO W ER<br />

ON<br />

CHECK EACH BOILER<br />

ELEM ENT ISAPPROX.<br />

19 O H M S<br />

YES<br />

CHECK AND REPLACE<br />

THE O VER-<br />

TEM PERATURE<br />

SW ITCHCONN3<br />

30 <strong>Installation</strong> & Servicing Instructions