The performance curves are based on the kinematic viscosity values = 1 mm 2 /s and density equal to 1000 Kg/m 3 . Curve tolerance according to ISO 9906.<br />
3 KVE 40 <strong>SETS</strong><br />
Liquid temperature range: from -15°C to +70°C<br />
Maximum ambient temperature: +40°C<br />
Max flow rate: 90 m 3 /h<br />
MODEL A B C H max<br />
DNA<br />
MANIFOLD<br />
DNM<br />
WEIGHT<br />
Kg<br />
3 KVE 40/3 1300 1200 260 1400 DN 100 - PN 10 DN 100 - PN 16 823<br />
3 KVE 40/4 1300 1200 260 1400 DN 100 - PN 10 DN 100 - PN 16 850<br />
3 KVE 40/5 1300 1200 260 1400 DN 100 - PN 10 DN 100 - PN 16 882<br />
3 KVE 40/6 1300 1200 260 1400 DN 100 - PN 10 DN 100 - PN 25 1036<br />
MODEL<br />
3 KVE 40/3<br />
VOLTAGE<br />
50 Hz<br />
3x400 V ~<br />
P2 NOMINAL<br />
kW<br />
HP<br />
3x5,5<br />
3x7,5<br />
In<br />
A<br />
3x12<br />
Q MIN - MAX<br />
m 3 /h<br />
8 - 90<br />
ADJUSTABLE PRESSURE<br />
MAX - MIN BAR<br />
7 - 3<br />
3 KVE 40/4<br />
3x400 V ~<br />
3x7,4<br />
3x10<br />
3x15<br />
8 - 90<br />
10 - 4<br />
3 KVE 40/5<br />
3x400 V ~<br />
3x9,2<br />
3x12,5<br />
3x18<br />
8 - 90<br />
12,5 - 5<br />
3 KVE 40/6<br />
3x400 V ~<br />
3x11<br />
3x15<br />
3x22<br />
8 - 90<br />
15 - 6,5<br />
Units with unitary power over 7.5 kW: star-delta starting for second and third pump<br />