Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
The performance curves are based on the kinematic viscosity values = 1 mm 2 /s and density equal to 1000 Kg/m 3 . Curve tolerance according to ISO 9906.<br />
3 KV 40 <strong>SETS</strong><br />
Liquid temperature range: from -15°C to +70°C<br />
Maximum ambient temperature: +40°C<br />
Max flow rate: 90 m 3 /h<br />
MODEL<br />
A B C D E G H O P I L M Fxn°<br />
Ø MANIFOLD<br />
DNA (suc.) DNM (del.)<br />
WEIGHT<br />
Kg<br />
3 KV 40/3 1300 1200 260 425 1030 1250 1030 450 250 135 220 180 18x8 DN 100 - PN 16 DN 100 - PN 16 813<br />
3 KV 40/4 1300 1200 260 470 1030 1250 1080 450 250 135 220 180 18x8 DN 100 - PN 16 DN 100 - PN 16 840<br />
3 KV 40/5 1300 1200 260 530 1030 1250 1130 450 250 135 220 180 18x8 DN 100 - PN 16 DN 100 - PN 16 873<br />
3 KV 40/6 1300 1200 260 575 1030 1250 1250 450 250 135 220 180 18x8 DN 100 - PN 16 DN 100 - PN 16 1026<br />
3 KV 40/7 1300 1200 260 625 1030 1250 1375 450 250 135 220 180 18x8 DN 100 - PN 25 DN 100 - PN 25 1070<br />
3 KV 40/8 1300 1200 260 675 1030 1250 1425 450 250 135 220 180 18x8 DN 100 - PN 25 DN 100 - PN 25 1090<br />
MODEL<br />
VOLTAGE<br />
50 Hz<br />
P2 NOMINAL<br />
kW HP<br />
In<br />
A<br />
FLOW RATE<br />
m 3 /h (1)<br />
PRESSURE<br />
SWITCH SET.<br />
BAR<br />
MAX.<br />
PRESSURE<br />
OBTAINABLE<br />
BAR<br />
PILOT PUMP *<br />
P2<br />
TYPE<br />
kW<br />
HP<br />
3 KV 40/3 T<br />
3x400 V ~<br />
3x5,5<br />
3x7,5<br />
3x12<br />
90,0-24,0<br />
5÷7<br />
7,85<br />
KV 3/12 T<br />
1,5<br />
2<br />
3 KV 40/4 T<br />
3x400 V ~<br />
3x7,5<br />
3x10<br />
3x15<br />
90,0-24,0<br />
7÷9<br />
10,4<br />
KV 3/15 T<br />
1,85<br />
2,5<br />
3 KV 40/5 T<br />
3x400 V ~<br />
3x9,2<br />
3x12,5<br />
3x18<br />
90,0-24,0<br />
9÷11<br />
13<br />
KV 3/18 T<br />
2,2<br />
3<br />
3 KV 40/6 T<br />
3x400 V ~<br />
3x11<br />
3x15<br />
3x22<br />
90,0-24,0<br />
11÷13<br />
15,7<br />
–<br />
–<br />
–<br />
3 KV 40/7 T<br />
3x400 V ~<br />
3x15<br />
3x20<br />
3x30<br />
90,0-24,0<br />
13÷15<br />
18,5<br />
–<br />
–<br />
–<br />
3 KV 40/8 T<br />
3x400 V ~<br />
3x15<br />
3x20<br />
3x30<br />
90,0-24,0<br />
15÷17<br />
21<br />
–<br />
–<br />
–<br />
(1) All data refer to groups considering the service pumps.<br />
* Pilot pump on request<br />
52<br />
®