The exchange system can be adjusted on the HYDROCONTROLLER in the following three ways:<br />

1) The Inverter commands a different pump<br />

at the end of each operating cycle (standard setting)<br />

2) The Inverter commands a different pump<br />

every 12 - 24 hours (adjustable)<br />

3) The Inverter always commands pump n° 1<br />

(adjustable by the user)<br />

If the electronics should fail, the HYDROCONTROLLER automatically switches the unit to the emergency pressure<br />

switch mode for pumps 2 and 3 in order to ensure continuous operation, though not at constant pressure.<br />

FEATURES OF THE ELECTRICAL PANEL<br />

Electrical control panel housed in an IP 55 metal box and attached to the base of the electric pumps.<br />

The panel is self-protected and protects the pumps from overloads and short-circuits.<br />

The panel is supplied standard with:<br />

• operating status display indicators (running - pumps shut-down, voltage presence) and alarm status<br />

(dry run – minimum pressure).<br />

• HYDROCONTROLLER control unit with backlit display<br />

• MANUAL - 0 – AUTOMATIC mode switch<br />

• Contacts for remote alarm signalling (Inverter alarm – pump shut-down – dry run – over pressure)<br />

The electrical panel can be connected to:<br />

• RS 485 output for unit control and supervision on a Personal Computer (*)<br />

• Float or pressure switch KIT as protection against operation without water (*)<br />

• Maximum pressure switch KIT (*)<br />

(*) Optional items available on request<br />

FEATURES OF THE HYDROCONTROLLER<br />

The easily accessible and simple programming control unit has four buttons as standard for programming the main<br />

parameters:<br />

- the language in which the parameters are displayed (Italian-English-French-German-Spanish)<br />

- the pressure to be constantly maintained<br />

- unit input pressure<br />

- correction constants (proportional and correction factor delay)<br />

- second and third pump engagement delay<br />

- plant load loss compensation<br />

- inverter-controlled pump exchange system<br />