Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
The performance curves are based on the kinematic viscosity values = 1 mm 2 /s and density equal to 1000 kg/m 3 . Curve tolerance according to ISO 9906.<br />
2 KDN 40 <strong>SETS</strong><br />
FIRE-FIGHTING TO UNI 9490-10779<br />
WITH 1 ELECTRIC PUMP NKP-G AND DIESEL 1 MOTOR PUMP KDN<br />
Pumped liquid temperature range: from -15°C to +70°C<br />
Maximum ambient temperature: from +4°C to +40°C<br />
Max flow rate: 68 m 3 /h<br />
Performance curves related to one functioning pump only.<br />
MODEL<br />
VOLTAGE<br />
(1)<br />
50 Hz<br />
TYPE<br />
PILOT PUMP *<br />
ELECTRIC PUMP<br />
P2 NOMINAL<br />
PILOT PUMP<br />
kW<br />
HP<br />
FLOW METER<br />
2 KDN/P 40-160/172 3x400 V + N ~ JET 251 NKP-G 40-160/172 8,6 12 7,5 10 1,85 2,5 2P S.40 - DN 65<br />
2 KDN/P 40-200/210 3x400 V + N ~ JET 251 NKP-G 40-200/210 13,5 18 11 15 1,85 2,5 2P S.40 - DN 65<br />
2 KDN/P 40-250/230 3x400 V + N ~ JET 251 NKP-G 40-250/230 17,7 24 15 20 1,85 2,5 2P S.40 - DN 65<br />
2 KDN/P 40-250/245 3x400 V + N ~ JET 251 NKP-G 40-250/245 17,7 24 18,5 25 1,85 2,5 2P S.40 - DN 65<br />
2 KDN/P 40-250/260 3x400 V + N ~ JET 251 NKP-G 40-250/260 21 28 22 30 1,85 2,5 2P S.40 - DN 65<br />
* Pilot pump on request<br />
** Continuous power (NA ISO 3046 ICXN). The motor can supply +10% of the continuous power (UNI 9490 4.9.5.1.).<br />
(1)<br />
1x220/240 V motor pump battery charger supply<br />
P2 NOMINAL<br />
DIESEL ELECTRIC<br />
PUMP ** PUMP<br />
kW HP kW HP<br />
161<br />
®