7 The parameterized<br />
Emergency-off function is<br />
shown.<br />
8 Select Double channel<br />
dependent Emergency-off<br />
Adding a<br />
Safety<br />
Guard<br />
9 The example safety guard is<br />
implemented using two roller<br />
switches assigned to the same<br />
guard.<br />
As the switches are positioned<br />
to the left and right of the<br />
guard, the contacts are not<br />
forced directly; rather, there is<br />
a dependency between the<br />
two switches.<br />
On the left of the window,<br />
select the Safety guard<br />
module under Double channel<br />
dependent.<br />
A period of infinite is entered<br />
for the Synchronization time.<br />
This time defines the<br />
permissible delay of the<br />
lagging roller switch.<br />
Here the Local<br />
acknowledgement is with the<br />
Pushbutton on Slave address<br />
7.<br />
Confirm with OK.<br />
Optimized <strong>AS</strong>-<strong>Interface</strong> M238 <strong>Schneider</strong> <strong>Electric</strong> 100