U-SUPPORT: CH 50-2-1,5mm & CH100-1-1,5mm MG-U: 02<br />
A)<br />
S-M WB-200-CH50-2<br />
Thickness<br />
1.5 mm<br />
Height<br />
B)<br />
P y (KN)<br />
C)<br />
D)<br />
P x (KN)<br />
Width<br />
Items list:<br />
Function Type Thickness (.mm) Weight(kg) Art # HDG Art # SS #of Parts<br />
A) Welded Starter S-M WB-200-CH50-2 6 0,9 1302514** 1371698 2<br />
B) Mekano Channel S-M CH50-2(*kg/m) 1,5 1,7* 1302506 1371689 1<br />
C) Mekano Channel S-M CH100-1(*kg/m) 1,5 1,7* 1371649 1371685 1<br />
D) Self Lock Boltset S-M LS-NU-M10x20 10 0,05 1371980 1371983 12<br />
**) S-M WB-200-CH50-2 is delivered in carbon steel quality.<br />
Load Capacity: Mekano Channel CH 50-2 (v) & CH 100-1 (h)<br />
Height(mm) Width(mm) Capacity P y (KN) Capacity P x (KN)<br />
1000 250 13.4 4.5<br />
1000 500 8.8 2.9<br />
1000 750 6.4 2.1<br />
1000 1000 4.4 1.5<br />
1000 1250 4.2 1.4<br />
• Norsk Standard code NS3472/Eurocode 03/Norsok.<br />
• Capacity (KN) is calculated using point load on the centre of the horizontal <strong>support</strong>.<br />
• Piping: ULS – Ultimate Limit state – Load factor 1,3 – Material factor 1,15 on r = 210N/mm².<br />
• Other disciplines: SLS -. Load factor 1,0 – Material factor 1,15 on r = 210N/mm².<br />
• Deflection allowance piping: L/300 or 3 mm. Most conservative used.<br />
• Deflection allowance other disciplines: L/200<br />
• Section properties are based on effective values reduced for perforations.<br />
• Max loads Y(KN) and X(KN) are non-concurrent loads.<br />
• We do not recommend to use channel CH100-1-1,5 as horizontal <strong>support</strong> for widths > 1,2 m.<br />
For these applications please substitute to either CH100-1 double or CH100-2T-2mm.<br />