Cantilever SUPPORT: CH100-4-5mm<br />
MG-C: 09<br />
S-M WB-CH100-4<br />
A)<br />
P y (KN)<br />
B)<br />
C)<br />
Width<br />
Thickness<br />
3 mm<br />
P x (KN)<br />
Items list:<br />
Function Type Thickness (.mm) Weight(kg) Art # HDG Art # SS #of Parts<br />
A) Welded Starter S-M WB-CH100-4 6 3 1372606** 1372601 1<br />
B) Mekano Channel S-M CH100-4-5(*kg/m) 3 8,5* 1372530 1372531 1<br />
C) Self Lock Boltset S-M LS-NU-M10x130 10 0,05 N/A 1372950 4<br />
D) End Protection A-CH100-4 EP Plastic: PS60018 1<br />
**) S-M WB-CH100-4 is delivered in carbon steel quality.<br />
Load Capacity: Mekano Channel CH100-4-5<br />
Width(mm) Capacity DW P y (KN) Piping P y (KN) Piping P x (KN) Blast P y (KN) Blast P x (KN)<br />
200 38,0 25,0 8,3 75,0 50,0<br />
400 19,2 14,0 4,3 50,0 50,0<br />
600 13,0 9,6 3,2 30,0 50,0<br />
800 9,5 7,2 2,4 22,0 50,0<br />
1000 7,6 5,8 1,8 18,0 50,0<br />
• Norsk Standard code NS3472/Eurocode 03/Norsok.<br />
• Capacity (KN) is calculated using point load.<br />
• Piping: ULS – Ultimate Limit state – Load factor 1,3 – Material factor 1,15 on p = 210N/mm².<br />
• Other disciplines: SLS -. Load factor 1,0 – Material factor 1,15 on p = 210N/mm².<br />
• Deflection allowance piping: L/300 or 3 mm. Most conservative used.<br />
• Deflection allowance other disciplines: L/200<br />
• Section properties are based on effective values reduced for perforations.<br />
• For blast calculation p=450N/mm².<br />