U-SUPPORT: CH 50-2T-2mm<br />
MG-U: 04<br />
A)<br />
S-M WB-200-CH50-2<br />
Thickness<br />
2 mm<br />
Height<br />
B)<br />
P y (KN)<br />
C)<br />
D)<br />
P x (KN)<br />
Width<br />
Items list:<br />
Function Type Thickness (.mm) Weight(kg) Art # HDG Art # SS #of Parts<br />
A) Welded Starter S-M WB-200-CH50-2 6 0,9 1302514** 1371698 2<br />
B) Mekano Channel S-M CH50-2T2(*kg/m) 2 1,9* 1372187 1372182 1<br />
C) Angle Bracket S-M AB 55x55-10 4 0,2 1302494 1371712 2<br />
D) Self Lock Boltset S-M LS-NU-M10x20 10 0,05 1371980 1371983 14<br />
**) S-M WB-200-CH50-2 is delivered in carbon steel quality.<br />
Load Capacity: Mekano Channel CH 50-2T2 (v) & CH 50-2T2 (h)<br />
Height(mm) Width(mm) Capacity P y (KN) Capacity P x (KN)<br />
1000 250 7.3 2.4<br />
1000 500 4.7 1.6<br />
1000 750 3.5 1.2<br />
1000 1000 2.8 0.9<br />
1000 1250 2 0.7<br />
• Norsk Standard code NS3472/Eurocode 03/Norsok.<br />
• Capacity (KN) is calculated using point load on the centre of the horizontal <strong>support</strong>.<br />
• Piping: ULS – Ultimate Limit state – Load factor 1,3 – Material factor 1,15 on r = 210N/mm².<br />
• Other disciplines: SLS -. Load factor 1,0 – Material factor 1,15 on r = 210N/mm².<br />
• Deflection allowance piping: L/300 or 3 mm. Most conservative used.<br />
• Deflection allowance other disciplines: L/200<br />
• Section properties are based on effective values reduced for perforations.<br />
• Max loads Y(KN) and X(KN) are non-concurrent loads.<br />
• We do not recommend to use channel CH50-2T-2 as horizontal <strong>support</strong> for widths > 1,2 m.<br />
For these applications please substitute to either CH100-1 double or CH100-2T-2mm.<br />