Multidiscipline support systeM type MultiGrid⢠- JT Day Pty Ltd
Multidiscipline support systeM type MultiGrid⢠- JT Day Pty Ltd
Multidiscipline support systeM type MultiGrid⢠- JT Day Pty Ltd
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
T-SUPPORT: CH100-2T-2mm MG-T: 01<br />
A)<br />
S-M WB-200-CH100-2<br />
Thickness<br />
2 mm<br />
B)<br />
Height<br />
P y (KN)<br />
P y (KN)<br />
C)<br />
P x (KN)<br />
P x (KN)<br />
Width<br />
Items list:<br />
Function Type Thickness (.mm) Weight(kg) Art # HDG Art # SS #of Parts<br />
A) Welded Starter S-M WB-200-CH100-2 5 1,6 88619** 88618 1<br />
B) Mekano Channel S-M CH100-2T2(*kg/m) 2 3,8* 1372189 1372184 1<br />
C) Self Lock Boltset S-M LS-NU-M10x20 10 0,05 1371980 1371983 8<br />
**) S-M WB-200-CH100-2 is delivered in carbon steel quality.<br />
Mekano Channel CH 100-2T2 (v) & CH 100-2T2 (h)<br />
Height(mm) Width(mm) Capacity DW P y (KN) Piping P x (KN)<br />
600 200 3,10 1,0<br />
600 400 2,30 0,7<br />
600 600 1,60 0,5<br />
600 800 1,20 0,4<br />
• Norsk Standard code NS3472/Eurocode 03/Norsok.<br />
• Capacity (KN) is calculated using point load on the centre of the horizontal <strong>support</strong>.<br />
• Piping: ULS – Ultimate Limit state – Load factor 1,3 – Material factor 1,15 on p = 210N/mm².<br />
• Other disciplines: SLS -. Load factor 1,0 – Material factor 1,15 on p = 210N/mm².<br />
• Deflection allowance piping: L/300 or 3 mm. Most conservative used.<br />
• Deflection allowance other disciplines: L/200<br />
• Section properties are based on effective values reduced for perforations.<br />
• Please note that the capacity calculation for T-<strong>support</strong> is for even loading on both sides.<br />
• Max loads Y(KN) and X(KN) are non-concurrent loads.<br />
50