Cantilever SUPPORT: CH50-2T-2,5mm<br />
MG-C: 04<br />
S-M WB-200-CH50-2<br />
A)<br />
P y (KN)<br />
B)<br />
P x (KN)<br />
C)<br />
Width<br />
Thickness<br />
2.5 mm<br />
Items list:<br />
Function Type Thickness (.mm) Weight(kg) Art # HDG Art # SS #of Parts<br />
A) Welded Starter S-M WB-200-CH50-2 6 0,9 1302514** 1371698 1<br />
B) Mekano Channel S-M CH50-2T2,5(*kg/m) 2,5 5,3* 1372188 1372183 1<br />
C) Self Lock Boltset S-M LS-NU-M10x20 10 0,05 1371980 1371983 4<br />
**) S-M WB-200-CH50-2 is delivered in carbon steel quality.<br />
Load Capacity: Mekano Channel CH50-2T2,5<br />
Lenght(mm) Capacity DW P y (KN) Piping P y (KN) Piping P x (KN) Blast P y (KN) Blast P x (KN)<br />
200 2,4 1,9 0,6 5,5 10,0<br />
400 1,2 0,9 0,3 2,5 10,0<br />
600 0,8 0,6 0,2 1,8 10,0<br />
• Norsk Standard code NS3472/Eurocode 03/Norsok.<br />
• Capacity (KN) is calculated using point load.<br />
• Piping: ULS – Ultimate Limit state – Load factor 1,3 – Material factor 1,15 on p = 210N/mm².<br />
• Other disciplines: SLS -. Load factor 1,0 – Material factor 1,15 on p = 210N/mm².<br />
• Deflection allowance piping: L/300 or 3 mm. Most conservative used.<br />
• Deflection allowance other disciplines: L/200<br />
• Section properties are based on effective values reduced for perforations.<br />
• For blast calculation p=450N/mm².<br />