T-SUPPORT: CH100-2T-3mm MG-T: 04<br />
A)<br />
S-M WB-200-CH100-2<br />
B)<br />
Thickness<br />
3 mm<br />
C)<br />
P y (KN)<br />
Height<br />
P y (KN)<br />
P x (KN)<br />
P x (KN)<br />
Width<br />
Items list:<br />
Function Type Thickness (.mm) Weight(kg) Art # HDG Art # SS #of Parts<br />
A) Welded Starter S-M WB-200-CH100-2 5 1,6 88619** 88618 1<br />
B) Mekano Channel S-M CH100-2T3(*kg/m) 3 6* 1372190 1372185 1<br />
C) Self Lock Boltset S-M LS-NU-M10x20 10 0,05 1371980 1371983 8<br />
**) S-M WB-200-CH100-2 is delivered in carbon steel quality.<br />
Mekano Channel CH100-2T3 (v) & CH100-2T3 (h)<br />
Height(mm) Width(mm) Capacity DW P y (KN) Piping P y (KN) Piping P x (KN) Blast P y (KN) Blast P x (KN)<br />
1500 300 4,9 4,7 1,4 7,5 2,5<br />
1500 600 3,6 2,7 0,9 7,5 2,5<br />
1500 900 2,4 1,8 0,6 6 2<br />
1500 1200 1,8 1,3 0,43 4,5 1,5<br />
• Norsk Standard code NS3472/Eurocode 03/Norsok.<br />
• Capacity (KN) is calculated using point load on the centre of the horizontal <strong>support</strong>.<br />
• Piping: ULS – Ultimate Limit state – Load factor 1,3 – Material factor 1,15 on p = 210N/mm².<br />
• Other disciplines: SLS -. Load factor 1,0 – Material factor 1,15 on p = 210N/mm².<br />
• Deflection allowance piping: L/300 or 3 mm. Most conservative used.<br />
• Deflection allowance other disciplines: L/200<br />
• Section properties are based on effective values reduced for perforations.<br />
• For blast calculation p=450N/mm².<br />
• Please note that the capacity calculation for T-<strong>support</strong> is for even loading on both sides.<br />