© <strong>Siemens</strong> AG 2007<br />

<strong>Slaves</strong><br />

Modules with Special Functions<br />

Counter modules<br />

■ Overview<br />

This module is used to send hexadecimally coded count values<br />

(LSB=D0, MSB=D3) to a higher level controller. The count value<br />

is increased by one for each valid count pulse at terminal 8. Beginning<br />

at 0, the module counts up to 15 and then begins again<br />

at 0. The controller adopts the current value and determines the<br />

number of pulses between two host invocations through subtraction<br />

from the previous value. The total number of count<br />

pulses is determined by adding these differences.<br />

For the values sent to be unambiguous, no more than 15 count<br />

values are allowed between two host invocations or AS-Interface<br />

master invocations at terminal 8. The maximum permissible<br />

transmission frequency is calculated from these times:<br />

f TRmax = 15 / T max<br />

T max : maximum possible transmission time from the slave to the<br />

host<br />

Another condition for the maximum frequency is the pulse<br />

shaped required. For the counter to accept a pulse as valid, a<br />

Low must have been applied at the input for at least 300 µs and<br />

a High for at least 1 ms. This results in a controller-independent<br />

maximum frequency of<br />

f Cmax = 1 / 1.3 ms = 769 Hz for the counter module (see following<br />

graphic).<br />

If the time criterion stipulated in the graphic is violated, the count<br />

value is rejected.<br />

The counter is active only for the reset parameter P2 (default).<br />

The counter is deleted when P2 is set, and the incoming count<br />

pulses are not registered until after P2 is reset again.<br />

Note: A customized function block is necessary or must be<br />

programmed.<br />

ASi+ ASi-<br />

+<br />

ASi<br />

IN1<br />

ADDR<br />

IN1 -<br />

NSA0_00085<br />

Terminal 4: Bus connection ASi+<br />

Terminal 5: Bus connection ASi-<br />

Terminal 6: unused<br />

Terminal 7: Sensor supply+<br />

Terminal 8: Counter input<br />

Terminal 9: Sensor supply-<br />

5<br />

7 1 <br />

5 ) & "<br />

Connection options<br />

I<br />

! I<br />

J<br />

■ Selection and ordering data<br />

Version DT Order No. Price<br />

per PU<br />

Counter modules<br />

PU<br />

(UNIT,<br />

SET,<br />

M)<br />

PS* PG Weight<br />

per PU<br />

approx.<br />

kg<br />

• With screw terminal connection A 3RK1 200-0CE03-0AA2 1 1 unit 121 0.104<br />

• With spring-loaded terminal connection B 3RK1 200-0CG03-0AA2 1 1 unit 121 0.091<br />

3RK1 200-0CE03-0AA2<br />

3RK1 200-0CG03-0AA2<br />

* You can order this quantity or a multiple thereof.<br />

<strong>Siemens</strong> LV 1 Short Catalog · 01/2007<br />