31.07.2014 Views

Operation and assembly instruction (USA): 261463 (1.0 MB) - Dungs

Operation and assembly instruction (USA): 261463 (1.0 MB) - Dungs

Operation and assembly instruction (USA): 261463 (1.0 MB) - Dungs

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Specification DMA<br />

DMA<br />

The actuator drives from 0 to 90 degrees via 4 - 20 mA input signal. It can move in any direction <strong>and</strong> stop<br />

anywhere over the entire 90 degree stroke.<br />

[V] [A]<br />

[Hz] [VA]<br />

Electrical Rating<br />

110 - 120 VAC (+10/-15%) 50 - 60 Hz<br />

Max. Power Rating<br />

2.0 VA Holding, 5.4 VA Operating<br />

°F<br />

+120<br />

+15<br />

0<br />

Ambient Temperature<br />

+15 °F to +120 °F (-10 °C to +50 °C)<br />

19<br />

Chrome Steel Made in Germany<br />

[Ib-in]<br />

18<br />

NEMA<br />

Max. Torque Ratings<br />

Timing Holding Operating<br />

6 12.4 in-lb 5.3 in-lb<br />

12 24.8 in-lb 8.9 in-lb<br />

30 26.5 in-lb 17.7 in-lb<br />

Enclosure Rating<br />

NEMA Type 1/IP 40 enclosure (st<strong>and</strong>ard<br />

with DMA)<br />

NEMA Type 4/IP 65 enclosure availabel<br />

(P/N 240 456)<br />

Position Resolution<br />

0.25 mA resolution; minimum of 1.6°<br />

per step<br />

Max. Contact Rating for Auxiliary<br />

Switch<br />

1.5 Amps at 120 VAC 50/60 Hz<br />

Input Control<br />

4 to 20 mA<br />

Position Feedback or Slave Output<br />

4 to 20 mA; 500 ohm maximum impedance.<br />

Resistence across terminals 8<br />

& 10 is 250 Ohms.<br />

Repeatability: max +/- 2°<br />

Specification DMK<br />

DMK/6<br />

The butterfly control valve actuates from 0 to 90 degrees in either direction; it is not a tight shut-off valve.<br />

Input-side male thread <strong>and</strong> output-side female thread enable <strong>assembly</strong> directly to DUNGS shutoff valves.<br />

[PSI]<br />

Max. Pressure<br />

7 PSI (500 mbar) MH 194167<br />

Max. Differential Pressure for Optimal<br />

Performance<br />

1.5 PSI (100 mbar)<br />

Max. Body Pressure<br />

15 PSI (1000 mbar)<br />

°F<br />

+140<br />

+5<br />

0<br />

Ambient Temperature<br />

+5 °F to +140 °F (-15 °C to +60 °C)<br />

Actuator angle<br />

90 degrees from open to closed<br />

Mounting Position<br />

Multipoised<br />

Gas<br />

Gases<br />

Dry, natural gas, propane, butane;<br />

other noncorrosive gases. Suitable<br />

for up to 0.1 % by volume, dry H 2<br />

S.<br />

A “dry” gas has a dew point lower<br />

than +15 °F <strong>and</strong> its relative humidity<br />

is less than 60 %.<br />

M/CD • Karl <strong>Dungs</strong> Inc. • DMA; DMK/6 • Edition 2012.06 • P/N 261 463<br />

2 … 4

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!