2 0 1 2 P R O D U C T C A T A L O G U E - Klima-Therm
2 0 1 2 P R O D U C T C A T A L O G U E - Klima-Therm
2 0 1 2 P R O D U C T C A T A L O G U E - Klima-Therm
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Easy Maintenance<br />
Outdoor units specifications<br />
Design for Easy Maintenance<br />
Dimensions<br />
166<br />
Model: AJYA36LALH / AJYA45LALH / AJYA54LALH<br />
650<br />
154<br />
(Unit : mm)<br />
Easy to read 7-segment LED : Confirm detail operational<br />
and trouble status without using specific equipment<br />
Error status can be checked easily via the indoor unit wired<br />
controller. An error code is displayed on a liquid crystal<br />
screen.<br />
Wired Remote Controller<br />
370<br />
43(Liquid)<br />
51(Gas)<br />
(410)<br />
40<br />
Faulty unit number (Remote controller address)<br />
Error code<br />
32<br />
36<br />
970 32 370 12<br />
7-segment LED<br />
Terminal blocks (Transmission)<br />
SU MO TU WE TH FR SA<br />
Terminal blocks (Power)<br />
Simple Remote Controller<br />
1334<br />
Remote controller address<br />
3-Way valve (Liquid)<br />
907<br />
1000<br />
Movable PCB panel<br />
Easier for maintenance work<br />
behind the PCB<br />
Error code<br />
21<br />
Ø28 (Cable port)<br />
131<br />
87<br />
89<br />
3-Way valve (Gas)<br />
Ø28 (Cable port)<br />
25<br />
50 95<br />
Pipe port<br />
279<br />
(Liquid valve)<br />
297<br />
(Gas valve)<br />
120<br />
111<br />
155<br />
50<br />
142<br />
70<br />
Ø28 (Cable port)<br />
21 55<br />
Ø28 (Cable port)<br />
Pipe port<br />
21 65<br />
50<br />
Ø28 (Cable port)<br />
Ø28 (Cable port)<br />
Pipe port<br />
Emergency Stop Function<br />
341<br />
305<br />
227<br />
A<br />
65 15<br />
50 14<br />
Detail<br />
A<br />
Emergency alarm can be received by indoor,<br />
outdoor units, Central Remote Controller or<br />
Touch Panel Controller when they received it,<br />
all units will be stopped.<br />
Note : In case of received Emergency alarm by<br />
Indoor / outdoor unit : All units connected within<br />
same refrigerant system will be stopped.<br />
Central Remote Controller or Touch Panel<br />
Controller : all units connected within VRF network<br />
system with Central Remote Controller or Touch<br />
Panel Controller will be stopped.<br />
Trouble diagnosis by Service Tool<br />
Connection to Service Tool<br />
• Detail operation status and recent error history can be<br />
checked and analyzed by using Service Tool.<br />
• Last 5 min. operation memory can be also recorded.<br />
Central<br />
Remote Controller<br />
or<br />
Touch Panel<br />
Controller<br />
Emergency<br />
stop function<br />
Emergency<br />
stop function<br />
Transmission cable (Non-polar 2 wires)<br />
Service Tool<br />
UTY-ASGX Software<br />
USB adaptor (Field supplied)<br />
Emergency<br />
stop function<br />
Specifications<br />
Rating Capacity range<br />
Model name<br />
Maximum Connectable Indoor Unit<br />
Indoor unit connectable capacity Cooling<br />
Power source<br />
Capacity<br />
Input power<br />
EER<br />
COP<br />
Air flow rate<br />
Sound<br />
pressure level<br />
Compressor motor output<br />
Heat exchanger fin<br />
Dimensions<br />
50<br />
Weight<br />
Refrigerant charge<br />
Connection<br />
pipe diameter<br />
Operation<br />
range<br />
438<br />
622<br />
HP<br />
Cooling<br />
Heating<br />
Cooling<br />
Heating<br />
Cooling<br />
Heating<br />
High<br />
Cooling<br />
Heating<br />
Height<br />
Width<br />
Depth<br />
kW<br />
kW<br />
kW<br />
kW<br />
W/W<br />
m 3 /h<br />
dB<br />
(A)<br />
mm<br />
mm<br />
mm<br />
kg<br />
kg<br />
Liquid<br />
mm<br />
Gas<br />
Cooling<br />
˚C<br />
Heating<br />
4<br />
AJYA36LALH<br />
6<br />
5.6 to 14.5<br />
Single-phase, ~230V, 50Hz<br />
11.2<br />
12.5<br />
2.80<br />
2.76<br />
4.00<br />
4.53<br />
6,200<br />
50<br />
52<br />
3.75<br />
Blue fin<br />
1,334<br />
970<br />
370<br />
117<br />
4.8<br />
ø9.52<br />
ø15.88<br />
-5 to 46<br />
-20 to 21<br />
Pipe & cable port<br />
5<br />
AJYA45LALH<br />
8<br />
7.0 to 18.2<br />
Single-phase, ~230V, 50Hz<br />
14.0<br />
16.0<br />
3.89<br />
3.81<br />
3.60<br />
4.20<br />
6,400<br />
51<br />
53<br />
3.75<br />
Blue fin<br />
1,334<br />
970<br />
370<br />
117<br />
5.3<br />
ø9.52<br />
ø15.88<br />
-5 to 46<br />
-20 to 21<br />
6<br />
AJYA54LALH<br />
9<br />
7.8 to 20.1<br />
Single-phase, ~230V, 50Hz<br />
15.5<br />
18.0<br />
4.49<br />
4.56<br />
3.45<br />
3.95<br />
6,900<br />
53<br />
55<br />
3.75<br />
Blue fin<br />
1,334<br />
970<br />
370<br />
117<br />
5.3<br />
ø9.52<br />
ø19.05<br />
-5 to 46<br />
-20 to 21<br />
Equipment Detail (Diagram)<br />
Note : Specifications are based on the following conditions.<br />
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.<br />
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.<br />
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.<br />
The protective function might work when using it outside the operation range.<br />
114<br />
115