14.11.2014 Views

ABB ACH550 - Full Version - Enervex

ABB ACH550 - Full Version - Enervex

ABB ACH550 - Full Version - Enervex

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

1-100 <strong>ACH550</strong>-UH User’s Manual<br />

Group 12: Constant Speeds<br />

Code Description Range Resolution Default S<br />

1202 CONST SPEED 1 0.0…500.0 Hz / 0.1 Hz / 6.0 Hz (US) /<br />

0…30000 rpm 1 rpm 360 rpm (US)<br />

Sets value for Constant Speed 1.<br />

• The range and units depend on parameter 9904 MOTOR CTRL MODE.<br />

• Range: 0…30000 rpm when 9904 = 1 (VECTOR:SPEED).<br />

• Range: 0…500 Hz when 9904 = 3 (SCALAR:FREQ).<br />

1203 CONST SPEED 2 0.0…500.0 Hz / 0.1 Hz / 12.0 Hz (US) /<br />

0…30000 rpm 1 rpm 720 rpm (US)<br />

Sets value for Constant Speed 2. See CONST SPEED 1 above.<br />

1204 CONST SPEED 3 0.0…500.0 Hz / 0.1 Hz / 18.0 Hz (US) /<br />

0…30000 rpm 1 rpm 1080 rpm (US)<br />

Sets value for Constant Speed 3. See CONST SPEED 1 above.<br />

1205 CONST SPEED 4 0.0…500.0 Hz / 0.1 Hz / 24.0 Hz (US) /<br />

0…30000 rpm 1 rpm 1440 rpm (US)<br />

Sets value for Constant Speed 4. See CONST SPEED 1 above.<br />

1206 CONST SPEED 5 0.0…500.0 Hz / 0.1 Hz / 30.0 Hz (US) /<br />

0…30000 rpm 1 rpm 1800 rpm (US)<br />

Sets value for Constant Speed 5. See CONST SPEED 1 above.<br />

1207 CONST SPEED 6 0.0…500.0 Hz / 0.1 Hz / 48.0 Hz (US) /<br />

0…30000 rpm 1 rpm 2880 rpm (US)<br />

Sets value for Constant Speed 6. See CONST SPEED 1 above.<br />

1208 CONST SPEED 7 0.0…500.0 Hz / 0.1 Hz / 60.0 Hz (US) /<br />

0…30000 rpm 1 rpm 3600 rpm (US)<br />

Sets value for Constant Speed 7. See CONST SPEED 1 above.<br />

Parameters