<strong>ACH550</strong>-UH User’s Manual 1-195<br />

Activate drive control functions – EFB<br />

Controlling the drive<br />

Fieldbus control of various drive functions requires configuration to:<br />

• Tell the drive to accept fieldbus control of the function.<br />

• Define as a fieldbus input, any drive data required for control.<br />

• Define as a fieldbus output, any control data required by the drive.<br />

The following sections describe, at a general level, the configuration required for<br />

each control function. For the protocol-specific details, see the document supplied<br />

with the FBA module.<br />

Start/stop direction control<br />

Using the fieldbus for start/stop/direction control of the drive requires:<br />

• Drive parameter values set as defined below.<br />

• Fieldbus controller supplied command(s) in the appropriate location. (The<br />

location is defined by the Protocol Reference, which is protocol dependent.)<br />

Note: EXT1 = REF1 typically used for follower;<br />

EXT2 = REF2 typically used for PID setpoint.<br />

Protocol Reference<br />

Drive Parameter Value Description<br />

1001 EXT1<br />

COMMANDS<br />

1002 EXT2<br />

COMMANDS<br />

10 (COMM) Start/Stop by<br />

fieldbus with Ext1<br />

selected.<br />

10 (COMM) Start/Stop by<br />

fieldbus with Ext2<br />

selected.<br />

1003 DIRECTION 3 (REQUEST) Direction by<br />

fieldbus.<br />

Modbus 1 DCU N2 FLN BACnet<br />

<strong>ABB</strong> DRV<br />

PROFILE<br />

40001<br />

bits 0…3<br />

40001<br />

bits 0…3<br />

40031<br />

bits 0, 1<br />

40031<br />

bits 0, 1<br />

4002/ 40031<br />

4003 2 bit 3<br />

BO1 24 BV10<br />

BO1 24 BV10<br />

BO2 22 BV11<br />

1. For Modbus, the protocol reference can depend on the profile used, hence two columns in these<br />

tables. One column refers to the <strong>ABB</strong> Drives profile, selected when parameter 5305 = 0 (<strong>ABB</strong> DRV<br />

LIM) or 5305 = 2 (<strong>ABB</strong> DRV FULL). The other column refers to the DCU profile selected when<br />

parameter 5305 = 1 (DCU PROFILE). See <strong>ABB</strong> control profiles technical data section.<br />

2. The reference provides direction control – a negative reference provides reverse rotation.<br />

Embedded fieldbus