<strong>ACH550</strong>-UH User’s Manual 1-65<br />

E-Clipse macro<br />

This macro configures for an E-Clipse Bypass device which can bypass the drive<br />

and connect the motor direct on-line. When using direct speed reference in AUTO<br />

mode or process PID, see General considerations on page 1-49.<br />

mA<br />

mA<br />

X1<br />

1 SCR<br />

2 AI1<br />

3 AGND<br />

4 10V<br />

5 AI2<br />

6 AGND<br />

7 AO1<br />

8 AO2<br />

9 AGND<br />

10 24V<br />

11 GND<br />

12 DCOM<br />

13 DI1<br />

14 DI2<br />

15 DI3<br />

16 DI4<br />

17 DI5<br />

18 DI6<br />

Signal cable shield (screen)<br />

Not configured<br />

Analog input circuit common<br />

Reference voltage 10 VDC<br />

Not configured<br />

Analog input circuit common<br />

Output frequency: 0(4)…20 mA<br />

Output current: 0(4)…20 mA<br />

Analog output circuit common<br />

Auxiliary voltage output +24 VDC<br />

Auxiliary voltage output common<br />

Digital input common for all<br />

Not configured<br />

Not configured<br />

Not configured<br />

Not configured<br />

Not configured<br />

Not configured<br />

ON ON<br />

J1 Jumper Settings<br />

ON<br />

AI1: 0(4)…20 mA<br />

AI2: 0(4)…20 mA<br />

1 2<br />

19 RO1C<br />

20 RO1A<br />

21 RO1B<br />

22 RO2C<br />

23 RO2A<br />

24 RO2B<br />

25 RO3C<br />

26 RO3A<br />

27 RO3B<br />

Relay output 1 (P 1401)<br />

Default operation: Started =>19 connected to 21<br />

Relay output 2 (P 1402)<br />

Default operation: Running =>22 connected to 24<br />

Relay output 3 (P 1403)<br />

Default operation: Fault (-1) =>25 connected to 27<br />

(Fault => 25 connected to 26)<br />

Parameters Changed Relative to HVAC Default<br />

Parameter Value Parameter Value<br />

9902 APPLIC MACRO 15 (E-CLIPSE) 1608 START ENABLE 1 7 (COMM)<br />

1001 EXT1 COMMANDS 10 (COMM) 5303 EFB BAUD RATE 76.8 KB/S<br />

1002 EXT2 COMMANDS 10 (COMM) 5304 EFB PARITY 2 (8 EVEN 1)<br />

1201 CONST SPEED SEL 0 (NOT SEL) 5305 EFB CTRL PROFILE 1 (DCU PROFILE)<br />

1601 RUN ENABLE 7 (COMM)<br />