<strong>ACH550</strong>-UH User’s Manual 1-83<br />

Group 01: Operating Data<br />

Code Description Range Resolution Default S<br />

0116 APPL BLK OUTPUT 0.0…100.0% 0.1% -<br />

(0.0…600.0% for torque)<br />

Application block output signal. Value is from either:<br />

• PFA control, if PFA Control is active, or<br />

• Parameter 0112 EXTERNAL REF 2.<br />

0118 DI 1-3 STATUS 000…111 (0…7 decimal) 1 -<br />

Status of the three digital inputs.<br />

• Status is displayed as a binary number.<br />

• 1 indicates that the input is activated.<br />

• 0 indicates that the input is deactivated.<br />

0119 DI 4-6 STATUS 000…111 (0…7 decimal) 1 -<br />

Status of the three digital inputs.<br />

• See parameter 0118 DI 1-3 STATUS.<br />

0120 AI 1 0.0…100.0% 0.1% -<br />

The relative value of analog input 1 in %.<br />

0121 AI 2 0.0…100.0% 0.1% -<br />

The relative value of analog input 2 in %.<br />

0122 RO 1-3 STATUS 000…111 (0…7 decimal) 1 -<br />

Status of the three relay outputs.<br />

• 1 indicates that the relay is energized.<br />

• 0 indicates that the relay is de-energized.<br />

DI 1 DI 2 DI 3<br />

RELAY 1 STATUS<br />

RELAY 2 STATUS<br />

RELAY 3 STATUS<br />

0123 RO 4-6 STATUS 000…111 (0…7 decimal) 1 -<br />

Status of the three relay outputs. Available if OREL-01 Relay Output Extension Module is installed.<br />

• See parameter 0122.<br />

0124 AO 1 0.0…20.0 mA 0.1 mA -<br />

The analog output 1 value in milliamperes.<br />

0125 AO 2 0.0…20.0 mA 0.1 mA -<br />

The analog output 2 value in milliamperes.<br />

0126 PID 1 OUTPUT -1000.0…1000.0% 0.1% -<br />

The PID controller 1 output value in %.<br />

0127 PID 2 OUTPUT -100.0…100.0% 0.1% -<br />

The PID controller 2 output value in %.<br />

0128 PID 1 SETPNT Unit and scale defined - -<br />

by par. 4006/4106 and<br />

4007/4107<br />

The PID 1 controller setpoint signal.<br />

• Units and scale defined by PID parameters.<br />

0129 PID 2 SETPNT Unit and scale defined - -<br />

by par. 4206 and 4207<br />

The PID 2 controller setpoint signal.<br />

• Units and scale defined by PID parameters.<br />

Parameters