<strong>ACH550</strong>-UH User’s Manual 1-125<br />

Group 25: CRITICAL SPEEDS<br />

This group defines up to three critical speeds or ranges of speeds that are to be<br />

avoided due, for example, to mechanical resonance problems at certain speeds.<br />

Group 25: Critical Speeds<br />

Code Description Range Resolution Default S<br />

2501 CRIT SPEED SEL 0, 1 1 0 (OFF)<br />

Sets the critical speeds function on or off. The critical speed<br />

function avoids specific speed ranges.<br />

0 = OFF – Disables the critical speeds function.<br />

1 = ON – Enables the critical speeds function.<br />

Example: To avoid speeds at which a fan system vibrates<br />

badly:<br />

• Determine problem speed ranges. Assume they are found to<br />

be: 18…23 Hz and 46…52 Hz.<br />

• Set 2501 CRIT SPEED SEL = 1.<br />

• Set 2502 CRIT SPEED 1 LO = 18 Hz.<br />

• Set 2503 CRIT SPEED 1 HI = 23 Hz.<br />

• Set 2504 CRIT SPEED 2 LO = 46 Hz.<br />

• Set 2505 CRIT SPEED 2 HI = 52 Hz.<br />

2502 CRIT SPEED 1 LO 0.0…500.0 Hz / 0.1 Hz / 0.0 Hz /<br />

0…30000 rpm 1 rpm 0 rpm<br />

Sets the minimum limit for critical speed range 1.<br />

• The value must be less than or equal to 2503 CRIT SPEED 1 HI.<br />

• Units are rpm, unless 9904 MOTOR CTRL MODE = 3 (SCALAR:FREQ), then units are Hz.<br />

2503 CRIT SPEED 1 HI 0.0…500.0 Hz / 0.1 Hz / 0.0 Hz /<br />

0…30000 rpm 1 rpm 0 rpm<br />

Sets the maximum limit for critical speed range 1.<br />

• The value must be greater than or equal to 2502 CRIT SPEED 1 LO.<br />

• Units are rpm, unless 9904 MOTOR CTRL MODE = 3 (SCALAR:FREQ), then units are Hz.<br />

2504 CRIT SPEED 2 LO 0.0…500.0 Hz / 0.1 Hz / 0.0 Hz /<br />

0…30000 rpm 1 rpm 0 rpm<br />

Sets the minimum limit for critical speed range 2.<br />

• See parameter 2502.<br />

2505 CRIT SPEED 2 HI 0.0…500.0 Hz / 0.1 Hz / 0.0 Hz /<br />

0…30000 rpm 1 rpm 0 rpm<br />

Sets the maximum limit for critical speed range 2.<br />

• See parameter 2503.<br />

2506 CRIT SPEED 3 LO 0.0…500.0 Hz / 0.1 Hz / 0.0 Hz /<br />

0…30000 rpm 1 rpm 0 rpm<br />

Sets the minimum limit for critical speed range 3.<br />

• See parameter 2502.<br />

2507 CRIT SPEED 3 HI 0.0…500.0 Hz / 0.1 Hz / 0.0 Hz /<br />

0…30000 rpm 1 rpm 0 rpm<br />

Sets the maximum limit for critical speed range 3.<br />

• See parameter 2503.<br />

52<br />

46<br />

23<br />

18<br />

f output<br />

f1L<br />

18<br />

f1H<br />

23<br />

f2L<br />

46<br />

f2H<br />

52<br />

f REF (Hz)<br />

Parameters