<strong>ACH550</strong>-UH User’s Manual 1-119<br />

Group 21: Start/Stop<br />

Code Description Range Resolution Default S<br />

2104 DC CURR CTL 0…2 1 0 (NOT SEL) <br />

Selects whether DC current is used for braking or DC Hold.<br />

Motor<br />

0 = NOT SEL – Disables the DC current operation.<br />

speed<br />

DC hold<br />

1 = DC HOLD – Enables the DC Hold function. See the diagram.<br />

• Requires parameter 9904 MOTOR CTRL MODE = 1 (VECTOR:SPEED)<br />

• Stops generating sinusoidal current and injects DC into the motor when<br />

T<br />

both the reference and the motor speed drop below the value of<br />

parameter 2105.<br />

Ref<br />

• When the reference rises above the level of parameter 2105 the drive<br />

resumes normal operation.<br />

2 = DC BRAKING – Enables the DC Injection Braking after modulation has DC hold<br />

stopped.<br />

speed<br />

T<br />

• If parameter 2102 STOP FUNCTION is 1 (COAST), braking is applied after<br />

start is removed.<br />

• If parameter 2102 STOP FUNCTION is 2 (RAMP), braking is applied after ramp.<br />

2105 DC HOLD SPEED 0…360 rpm 1 rpm 5 rpm<br />

Sets the speed for DC Hold. Requires that parameter 2104 DC HOLD CTL = 1 (DC HOLD).<br />

2106 DC CURR REF 0…100% 1% 30%<br />

Defines the DC current control reference as a percentage of parameter 9906 MOTOR NOM CURR.<br />

2107 DC BRAKE TIME 0.0…250.0 s 0.1 s 0.0 s<br />

Defines the DC brake time after modulation has stopped, if parameter 2104 is 2 (DC BRAKING).<br />

2108 START INHIBIT 0, 1 1 0 (OFF)<br />

Sets the Start inhibit function on or off. If the drive is not actively started and running, the Start inhibit function ignores<br />

a pending start command in any of the following situations and a new start command is required:<br />

• A fault is reset.<br />

• Run Enable (parameter 1601) activates while start command is active.<br />

• Mode changes from local to remote.<br />

• Control switches from EXT1 to EXT2.<br />

• Control switches from EXT2 to EXT1.<br />

0 = OFF – Disables the Start inhibit function.<br />

1 = ON – Enables the Start inhibit function.<br />

2109 EMERG STOP SEL -6…6 1 0 (NOT SEL)<br />

Defines control of the Emergency stop command. When activated:<br />

• Emergency stop decelerates the motor using the emergency stop ramp (parameter 2208 EMERG DEC TIME).<br />

• Requires an external stop command and removal of the emergency stop command before drive can restart.<br />

0 = NOT SEL – Disables the Emergency stop function through digital inputs.<br />

1 = DI1 – Defines digital input DI1 as the control for Emergency stop command.<br />

• Activating the digital input issues an Emergency stop command.<br />

• De-activating the digital input removes the Emergency stop command.<br />

2…6 = DI2…DI6 – Defines digital input DI2…DI6 as the control for Emergency stop command.<br />

•See DI1 above.<br />

-1 = DI1(INV) – Defines an inverted digital input DI1 as the control for Emergency stop command.<br />

• De-activating the digital input issues an Emergency stop command.<br />

• Activating the digital input removes the Emergency stop command.<br />

-2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the control for Emergency stop command.<br />

•See DI1(INV) above.<br />

2110 TORQ BOOST CURR 15…300% 1% 100%<br />

Sets the maximum supplied current during torque boost.<br />

• See parameter 2101 START FUNCTION.<br />

Parameters