Maximum energy absorption<br />
Surge currents of relatively long duration are required for testing maximum energy absorption capability.<br />
A rectangular wave of 2 ms according to IEC 60 (figure 8b) is commonly used for this test.<br />
In the product tables the maximum energy absorption is consequently defined for a surge current<br />
of 2 ms.<br />
8a<br />
8b<br />
Leading<br />
edge<br />
Figures 8a and b<br />
Peak<br />
Trailing edge<br />
T S Rise time in µs<br />
T r Decay time to half value in µs<br />
0 1 Nominal start<br />
I m Peak value<br />
T D<br />
T T<br />
Possible<br />
polarity reversal<br />
Duration of peak value (≈ 2 ms)<br />
Total duration<br />
Surge current waveforms of 8/20 µs and 2 ms to IEC 60 standard<br />