04.01.2015 Views

Service Handbook - AO Smith Water Heaters

Service Handbook - AO Smith Water Heaters

Service Handbook - AO Smith Water Heaters

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Gas Pressure<br />

The water heater covered in this <strong>Service</strong> Manual is rated at 100,000 Btu/hr input. It is certified for elevations<br />

up to 10,100 feet (3,078 meters). For higher elevations call the toll free support phone number shown on the<br />

back cover of this manual for technical assistance.<br />

Table 2<br />

†Manifold Offset Pressure Minimum Supply Pressure Maximum Supply Pressure<br />

NATURAL GAS PROPANE GAS NATURAL GAS PROPANE GAS NATURAL GAS PROPANE GAS<br />

0.24” W. C. (0.056 kPa) 0.17” W. C. (0.042 kPa) 3.5” W. C. (0.87 kPa) 8” W. C. (1.20 kPa) 14” W. C. (3.49 kPa) 14” W. C. (3.49 kPa)<br />

† Manifold offset pressures will vary. See the <strong>Service</strong> Notes below.<br />

<strong>Service</strong> Notes:<br />

• The manifold "offset" gas pressure is factory set and cannot be adjusted in the field.<br />

• The manifold offset gas pressure and the supply gas pressure can be measured at two pressure test<br />

ports on the water heater’s 24 Volt Gas Valve, see Figure 27 below. The manifold offset pressure test<br />

port is closest to the Combustion Blower, see Figure 28 on page 26. There is a needle valve in each test<br />

port that is opened/closed with a small slotted screwdriver. Turn the needle valve counter-clockwise to<br />

open the test port valve and clockwise to close it.<br />

• Manifold offset gas pressure will run close to 0” W.C. or lower (in a vacuum) depending on the current<br />

operating state, see Operating States on page 48. This pressure will be considerably lower, -5.00” W.C.<br />

to -7.50” W.C. during the Pre- Purge and Post-Purge operating states when the Combustion Blower is<br />

running at high speed and the 24 Volt Gas Valve is closed, see Venturi on page 22.<br />

• When the 24 Volt Gas Valve opens gas entering the Venturi will cause a rise in manifold offset gas<br />

pressure. Manifold offset gas pressures will typically be +0.24” W.C. on natural gas models and +0.17”<br />

W.C. on propane gas models during the Heating operating state. Keep in mind these pressures are<br />

approximate and will vary depending on the equivalent length of the vent and/or intake air pipe installed.<br />

• There is usually a drop in supply gas pressure noticed when the water heater’s 24 Volt Gas Valve opens<br />

during ignition. Seeing a corresponding rise in manifold offset pressure during ignition confirms the valve<br />

is opening and gas is flowing to the Burner, see Gas Flow Test on page 27.<br />

• A sustained drop in supply gas pressure of 1.5" W.C. or more during ignition may indicate the supply<br />

gas line is undersized. If the water heater is experiencing a sustained drop in supply gas pressure of<br />

1.5" W.C. or more and the water heater is experiencing repeated Ignition Failure fault conditions,<br />

intermittent loss of flame or rough starting ensure the supply gas line is sized in accordance with the<br />

current edition of National Fuel Gas Code (ANSI Z223.1/NFPA 54) or the Natural Gas and Propane<br />

Installation Code (CAN/CSA B149.1).<br />

PRESSURE<br />

TEST PORTS<br />

COMBUSTION<br />

BLOWER<br />

CONNECTION<br />

24 VOLT GAS VALVE<br />

SUPPLY GAS<br />

CONNECTION<br />

VENTURI<br />

COMBUSTION<br />

AIR INLET<br />

Figure 27<br />

Servicing should only be performed by a Qualified <strong>Service</strong> Agent<br />

25

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!