Service Handbook - AO Smith Water Heaters
Service Handbook - AO Smith Water Heaters
Service Handbook - AO Smith Water Heaters
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Gas Pressure<br />
The water heater covered in this <strong>Service</strong> Manual is rated at 100,000 Btu/hr input. It is certified for elevations<br />
up to 10,100 feet (3,078 meters). For higher elevations call the toll free support phone number shown on the<br />
back cover of this manual for technical assistance.<br />
Table 2<br />
†Manifold Offset Pressure Minimum Supply Pressure Maximum Supply Pressure<br />
NATURAL GAS PROPANE GAS NATURAL GAS PROPANE GAS NATURAL GAS PROPANE GAS<br />
0.24” W. C. (0.056 kPa) 0.17” W. C. (0.042 kPa) 3.5” W. C. (0.87 kPa) 8” W. C. (1.20 kPa) 14” W. C. (3.49 kPa) 14” W. C. (3.49 kPa)<br />
† Manifold offset pressures will vary. See the <strong>Service</strong> Notes below.<br />
<strong>Service</strong> Notes:<br />
• The manifold "offset" gas pressure is factory set and cannot be adjusted in the field.<br />
• The manifold offset gas pressure and the supply gas pressure can be measured at two pressure test<br />
ports on the water heater’s 24 Volt Gas Valve, see Figure 27 below. The manifold offset pressure test<br />
port is closest to the Combustion Blower, see Figure 28 on page 26. There is a needle valve in each test<br />
port that is opened/closed with a small slotted screwdriver. Turn the needle valve counter-clockwise to<br />
open the test port valve and clockwise to close it.<br />
• Manifold offset gas pressure will run close to 0” W.C. or lower (in a vacuum) depending on the current<br />
operating state, see Operating States on page 48. This pressure will be considerably lower, -5.00” W.C.<br />
to -7.50” W.C. during the Pre- Purge and Post-Purge operating states when the Combustion Blower is<br />
running at high speed and the 24 Volt Gas Valve is closed, see Venturi on page 22.<br />
• When the 24 Volt Gas Valve opens gas entering the Venturi will cause a rise in manifold offset gas<br />
pressure. Manifold offset gas pressures will typically be +0.24” W.C. on natural gas models and +0.17”<br />
W.C. on propane gas models during the Heating operating state. Keep in mind these pressures are<br />
approximate and will vary depending on the equivalent length of the vent and/or intake air pipe installed.<br />
• There is usually a drop in supply gas pressure noticed when the water heater’s 24 Volt Gas Valve opens<br />
during ignition. Seeing a corresponding rise in manifold offset pressure during ignition confirms the valve<br />
is opening and gas is flowing to the Burner, see Gas Flow Test on page 27.<br />
• A sustained drop in supply gas pressure of 1.5" W.C. or more during ignition may indicate the supply<br />
gas line is undersized. If the water heater is experiencing a sustained drop in supply gas pressure of<br />
1.5" W.C. or more and the water heater is experiencing repeated Ignition Failure fault conditions,<br />
intermittent loss of flame or rough starting ensure the supply gas line is sized in accordance with the<br />
current edition of National Fuel Gas Code (ANSI Z223.1/NFPA 54) or the Natural Gas and Propane<br />
Installation Code (CAN/CSA B149.1).<br />
PRESSURE<br />
TEST PORTS<br />
COMBUSTION<br />
BLOWER<br />
CONNECTION<br />
24 VOLT GAS VALVE<br />
SUPPLY GAS<br />
CONNECTION<br />
VENTURI<br />
COMBUSTION<br />
AIR INLET<br />
Figure 27<br />
Servicing should only be performed by a Qualified <strong>Service</strong> Agent<br />
25