Gas Flow Test<br />

The following illustrations show the approximate pressures for the manifold offset and supply gas for the<br />

Standby, Pre-Purge and Heating operating states during a normal heating sequence. Notice how the manifold<br />

offset pressure starts at 0" W.C. in the Standby operating state, falls to a deep vacuum during the Pre-Purge<br />

state and then rises to a slight positive pressure when the 24 Volt Gas Valve is energized during the Heating<br />

state. Also notice how the supply gas pressure remains constant until the 24 Volt Gas valve is energized at<br />

which point it drops slightly.<br />

Follow the procedure to connect two digital manometers to the 24 Volt Gas Valve in the Gas Pressure Test<br />

on page 26. Observe the pressure changes during the three operating states listed in Figure 29 below.<br />

The drop in supply pressure and corresponding rise in manifold offset pressure, between Steps 2 and 3,<br />

proves the 24 Volt Gas valve is opening and that fuel gas is flowing through the valve.<br />

1<br />

OPERATING STATE:<br />

• STANDBY<br />

CONDITIONS:<br />

• COMBUSTION BLOWER OFF<br />

• 24 VOLT GAS VALVE OFF<br />

PRESSURE READINGS:<br />

• MANIFOLD OFFSET:<br />

• SUPPLY GAS:<br />

0.00” W.C.<br />

+8.41” W.C.<br />

2<br />

OPERATING STATE:<br />

• PRE-PURGE<br />

CONDITIONS:<br />

• COMBUSTION BLOWER ON<br />

• 24 VOLT GAS VALVE OFF<br />

PRESSURE READINGS:<br />

• MANIFOLD OFFSET:<br />

• SUPPLY GAS:<br />

-5.33” W.C.<br />

+8.41” W.C.<br />

3<br />

OPERATING STATE:<br />

• HEATING<br />

CONDITIONS:<br />

• COMBUSTION BLOWER ON<br />

• 24 VOLT GAS VALVE ON<br />

PRESSURE READINGS:<br />

• MANIFOLD OFFSET:<br />

• SUPPLY GAS:<br />

0.07” W.C.<br />

+7.75” W.C.<br />

Figure 29<br />

Servicing should only be performed by a Qualified <strong>Service</strong> Agent<br />

27