CCB Circuit Board Layout<br />

CCB (CENTRAL CONTROL BOARD)<br />

1<br />

2<br />

1<br />

2<br />

1<br />

2 1<br />

3<br />

4<br />

5<br />

J1<br />

3<br />

4<br />

J2<br />

4<br />

J3<br />

2<br />

J5<br />

J4<br />

15<br />

12<br />

9<br />

6<br />

3<br />

J6<br />

14<br />

11<br />

8<br />

5<br />

2<br />

Ext<br />

Input<br />

1 Retry<br />

Use Yes<br />

Type Tstat<br />

Spare<br />

1 2 3 4<br />

OPEN<br />

3<br />

Retries<br />

No<br />

Vent<br />

Spare<br />

S1 DIPSWITCH<br />

13<br />

10<br />

7<br />

J7 4 3 2 1<br />

4<br />

1<br />

J9<br />

J10<br />

1 3<br />

J13<br />

1 5<br />

2 6<br />

J15<br />

J16<br />

J11<br />

2<br />

4<br />

3<br />

7<br />

1<br />

4<br />

8<br />

2<br />

Ext<br />

Input<br />

S1 DIPSWITCH DETAIL<br />

Use<br />

Type<br />

1 Retry<br />

Yes<br />

Tstat<br />

1 2 3 4<br />

3<br />

Retries<br />

Spare<br />

Spare<br />

Dipswitch Operation:<br />

Along one side of the dipswitch array there are numbers, 1-4. On the other side of the dipswitch<br />

is the word “OPEN.” The dipswitches are rocker type switches, if one side of the rocker is down the<br />

other side will be up. Pressing a rocker down on the side of the array labeled “OPEN,” opens the switch.<br />

Pressing a rocker down on the side of the array labeled with the numbers 1-4 closes the dipswitch.<br />

OPEN<br />

CHANGING NUMBER OF IGNITION TRIALS BEFORE LOCK OUT<br />

No<br />

Vent<br />

NOTE: Always turn off power to the water heater before changing dipswitch settings.<br />

Set dipswitch #4 to the open position for 1 trial for ignition before Ignition Failure lock out. Set dipswitch<br />

#4 to the closed position for 3 trials for ignition before Ignition Failure lock out.<br />

Figure 41<br />

Servicing should only be performed by a Qualified <strong>Service</strong> Agent<br />