Status Icons<br />
The Status Icons are displayed on the Desktop Screen and convey operational and diagnostic information.<br />
The icons are described in the table below.<br />
Table 5<br />
Icon<br />
Description<br />
<strong>Water</strong> temperature in the tank has fallen. Shaded area of the animated thermometer icon will rise and fall in response to<br />
water temperature in the storage tank as sensed from the Temperature Probe(s).<br />
<strong>Water</strong> temperature in the tank has reached the Operating Set Point. The Control System enters the Standby operating state.<br />
The control is unable to initiate a heating cycle. This will happen whenever a Fault condition is detected by the Control<br />
System or when the Enable/Disable circuit is an open circuit.<br />
The Combustion Blower is being energized.<br />
The Blower Prover pressure switch contacts have closed. The check mark icon is visual confirmation of contact closure.<br />
The Igniter is being energized.<br />
The Igniter has been energized and the Control System has sensed the required minimum Igniter current. The check mark<br />
icon is visual confirmation of minimum Igniter current.<br />
OFF<br />
The 24 Volt Gas Valve is being energized.<br />
GAS<br />
O<br />
N<br />
The Control System has sensed flame at the Burner from the Flame Sensor.<br />
The Control System has declared a Fault condition and must be inspected/serviced by a Qualified <strong>Service</strong> Agent. Fault<br />
message details can be viewed in the Current Fault menu. Heating operation is disabled (Control System lock out) until the<br />
condition that caused the Fault is corrected. Power to the water heater must be cycled off and on to reset the Control System.<br />
Note: Cycling power will not reset the Control System if the condition that caused the Fault has not been corrected.<br />
The Control System has declared an Alert condition and must be inspected/serviced by a Qualified <strong>Service</strong> Agent. The water<br />
heater will continue to operate during an Alert condition.<br />
Servicing should only be performed by a Qualified <strong>Service</strong> Agent<br />